43
5.2.9 Flow Meter, Contactor Type
Input Details
The details for this type of input include the total volume accumulated through the flow meter,
alarms, and the current type of input setting.
Settings
Touch the Settings icon to view or change the settings related to the sensor.
Totalizer Alarm
A high limit on the total volume of water accumulated may be set.
Reset Flow Total
Enter this menu to reset the accumulated flow total to 0. Touch Confirm to
accept, Cancel to leave the total at the previous value and go back.
Volume/Contact
Enter the volume of water that needs to go through the flow meter in order
to generate a contact closure.
Flow Units
Select the units of measure for the water volume.
Name
The name used to identify the sensor may be changed.
Type
Select the type of sensor to be connected to the digital input channel.
5.2.10 Flow Meter, Paddlewheel Type
Input Details
The details for this type of input include the current flow rate, total volume accumulated through the
flow meter, alarms, and the current type of input setting.
Settings
Touch the Settings icon to view or change the settings related to the sensor.
Totalizer Alarm
A high limit on the total volume of water accumulated may be set.
Reset Flow Total
Enter this menu to reset the accumulated flow total to 0. Touch Confirm to
accept, Cancel to leave the total at the previous value and go back.
K Factor
Enter the pulses generated by the paddlewheel per unit volume of water.
Flow Units
Select the units of measure for the water volume.
Rate Units
Select the units of measure for the flow rate time base.
Name
The name used to identify the sensor may be changed.
Type
Select the type of sensor to be connected to the digital input channel.
Summary of Contents for W600 Series
Page 15: ...12 Figure 1 Conduit Wiring ...
Page 36: ...33 Overview of the menu structure ...
Page 37: ...34 ...
Page 74: ...71 WCT600 Sensor option BD and FD ...
Page 75: ...72 WCT600 Sensor option BN or FN ...
Page 76: ...73 WCT600 Sensor option BA BB BC FA FB FC ...
Page 77: ...74 WCT600 Sensor option DE DF ...
Page 78: ...75 WCT600 Sensor option DN ...
Page 79: ...76 WCT600 Sensor option HA HB and HC ...
Page 80: ...77 WCT600 Sensor option HD ...
Page 81: ...78 WCT600 Sensor option HN ...
Page 82: ...79 WDS600 Sensor option FF or FN ...
Page 83: ...80 WDS600 Sensor option PN ...
Page 84: ...81 WDS600 Sensor option PX ...
Page 85: ...82 WPH600 Sensor option PN ...
Page 86: ...83 WPH600 Sensor option PX ...