Installation
• 17
Fieldbus Dependent I/O Module
PROFIBUS DP
Attention
When providing a separate output supply voltage to a group of 8 outputs, the
supply voltage common must be terminated on the base module using the 0 V
potential of the WAGO-I/O-SYSTEM 752 (blue terminal block).
The entire current load is applied to the common terminal connection. If more
than 6 Amps is applied to the common terminals, separate terminal blocks
should be used. Connect all common connections to the terminal blocks, and
then connect the 752 common to the terminal blocks. This row of terminal
blocks will be wired back to the source common of the supply potential.
4.2.5 Connection of the Output Signals
The output signal terminals are identified by the imprint “OUTPUT” on the
base module.
Two terminals are available for each digital output. The terminals for one out-
put are shown superimposed.
0 V
1
2
3
33 34 35
Output
grey
Color
blue
Vertical connection group for one channel
Fig. 4-12: Actuator connection
g1xxx07e
The positive connection of an actuator is wired to the grey output terminal
block. The negative connection of an actuator is wired to the blue output ter-
minal block.
41 42 43
9
10 11
1
2
3
33 34 35
grey
Color
blue
Fig. 4-13: Examples of an actuator connection
g1xxx09e