RS232,TTY,RS485 750-650,651,653
:$*2
Ç
,
2
Ç
6<67(0
9
- As soon as TA = TR, the data has been transferred to the output buffer.
Input byte 0
Status byte
Input byte 2
Input byte 1
XX
0XXX.XXX1 XX
XX
The data is still being transferred.
XX
0XXX.XXX0 XX
XX
Data transfer completed.
Receiving the character chain “WAGO”
- As soon as RA
≠
RR, the input bytes contain data.
Output byte 0
Control yte
Output byte 2
Output byte 1
XX
0XXX.000X
XX
XX
Input byte 0
Status byte
Input byte 2
Input byte 1
XX
0XXX.0X0X XX
XX
No received data available.
‘W’ (0 x 57)
0011.0X1X
‘G’ (0 x 47)
‘A’ (0 x 41)
The information is in the input bytes.
- After the 3 characters have been processed, RA is inverted.
Output byte 0
Control byte
Output byte 2
Output byte 1
XX
0XXX.001X
XX
XX
- If RA
≠
RR, the receiving of additional characters will continue.
Input byte 0
Status byte
Input byte 2
Input byte 1
XX
0XXX.0X1X XX
XX
No received data available.
‘O’ (0 x 4F)
0001.0X0X
XX
XX
The information is in the input bytes.
- After the characters have been processed, RA is inverted.
Output byte 0
Control byte
Output byte
Output byte
XX
0XXX.000X
XX
XX
Notes:
0 x 23 is a hexadecimal value
0101.1001 is a binary value
An X indicates that this particular value has no importance.
XX indicates that the whole value has no importance.
Status Indicators:
The 3 green LEDs have the following function:
Function
Non-Function
Output Status TxD
Input Status RxD