Analog Outputs 750-552, 554, 584
:$*2
Ç
,
2
Ç
6<67(0
3
The numerical format for Siemens
In addition to the full 16 bit indication of the measured value it is possible to use the
‘Siemens format’. The measured value is represented by the most significant 12 Bits.
The 4 least significant Bits have no function. (750-584)
Output
current 4-20
mA
Binary value
Hex.
Dec.
20
0100 0000 0000 XXXX
40 00
16384
16
0011 0000 0000 XXXX
30 00
12288
12
0010 0000 0000 XXXX
20 00
8192
8
0001 0000 0000 XXXX
10 00
4096
4.015
0000 0000 0001 XXXX
00 10
16
4
0000 0000 0000 XXXX
00 00
0
If you have questions about the formatting of this data, please contact WAGO for
I/O System technical support.