Input for PT100 750-461, 481
:$*2
Ç
,
2
Ç
6<67(0
3
The numerical format
All temperature values will be shown in a unit numerical format. If the mode
‘DEFAULT’ is selected each bit corresponds to 0.1°C. The possible numerical range
refers to the standardized temperature range of the used sensors. The following table
will explain the numerical format on a preset PT100
. In the third column the numerical
format for PT1000 (750-461/000-003) is explained.
Temperature
°C
Voltage
(Ohm)
Voltage
(Ohm)
Binary Value
Hex.
Dec.
>400
850
390.481
1384,998
0010 0001 0011 0100
2134
8500
100
138.506
1099,299
0000 0011 1110 1000
03E8
1000
25.5
109.929
1000,391
0000 0000 1111 1111
00FF
255
0.1
100.039
1000
0000 0000 0000 0001
0001
1
0
100
999,619
0000 0000 0000 0000
0000
0
-0.1
99.970
901,929
1111 1111 1111 1111
FFFF
-1
-25.5
90.389
184,936
1111 1111 0000 0001
FF01
-255
-200
18.192
1111 1000 0011 0000
F830
-2000
<18
1000 0000 0000 0000
8000
-32767
Table 1