background image

 

 

Important Notes 

  

  5 

 

 

Legal Bases 

 

WAGO-I/O-SYSTEM 750 
I/O Modules 

All responsible persons have to familiarize themselves with the underlying 
legal standards to be applied. WAGO Kontakttechnik GmbH & Co. KG does 
not assume any liability whatsoever resulting from improper handling and 
damage incurred to both WAGO´s own and third-party products by 
disregarding detailed information in this Manual. 

1.1.3 Use of the 750 Series in Compliance with Underlying Provisions 

Couplers, controllers and I/O modules found in the modular WAGO-I/O-
SYSTEM 750 receive digital and analog signals from sensors and transmit 
them to the actuators or higher-level control systems. Using programmable 
controllers, the signals can also be (pre-)processed. 

The components have been developed for use in an environment that meets 
the IP20 protection class criteria. Protection against finger injury and solid 
impurities up to 12.5 mm diameter is assured; protection against water damage 
is not ensured. Unless otherwise specified, operation of the components in wet 
and dusty environments is prohibited. 

1.1.4 Technical Condition of Specified Devices 

The components to be supplied Ex Works, are equipped with hardware and 
software configurations, which meet the individual application requirements. 
Changes in hardware, software and firmware are permitted exclusively within 
the framework of the various alternatives that are documented in the specific 
manuals. WAGO Kontakttechnik GmbH & Co. KG will be exempted from 
any liability in case of changes in hardware or software as well as to non-
compliant usage of components. 

Please send your request for modified and new hardware or software 
configurations directly to WAGO Kontakttechnik GmbH & Co. KG. 

Summary of Contents for I/O SYSTEM 750 750-641

Page 1: ...Fieldbus Independent I O Modules DALI DSI Master Module 750 641 Manual Version 1 2 0...

Page 2: ...571 8 87 5 55 Fax 49 0 571 8 87 85 55 E Mail support wago com Every conceivable measure has been taken to ensure the correctness and com pleteness of this documentation However as errors can never be...

Page 3: ...iption 11 2 1 1 3 Display Elements 12 2 1 1 4 Schematic Diagram 13 2 1 1 5 Technical Data 13 2 1 1 6 Process Data 14 2 1 1 6 1 Implementing a PFC Programming Fieldbus Controller 15 2 1 1 6 2 Implement...

Page 4: ...ght to provide for any alterations or modifications that serve to increase the efficiency of technical progress WAGO Kontakttechnik GmbH Co KG owns all rights arising from the granting of patents or f...

Page 5: ...loped for use in an environment that meets the IP20 protection class criteria Protection against finger injury and solid impurities up to 12 5 mm diameter is assured protection against water damage is...

Page 6: ...Emergency stop functions and equipment shall not be made ineffective See relevant standards e g DIN EN 418 The equipment of your system shall be conform to EMC guidelines so that any electromagnetic i...

Page 7: ...bserved to ensure smooth and efficient operation ESD Electrostatic Discharge Warning of damage to the components through electrostatic discharge Observe the precautionary measure for handling componen...

Page 8: ...n a long term basis Warning The components are not resistant against materials having seeping and insulating properties Belonging to this group of materials is e g aerosols silicones triglycerides fou...

Page 9: ...u e g File New END Pushbuttons are marked as bold with small capitals e g ENTER Keys are marked bold within angle brackets e g F5 Courier The print font for program codes is Courier e g END_VAR 1 6 Nu...

Page 10: ...e DALI DSI Master Module Attention Accessories required WAGO DC DC converter Item No 288 895 2 1 1 1 View _ 13 14 C D B A 750 641 Bus Bus Bus _ Bus DALI bus U_DALI Data contacts DALI bus DC 18 V DALI...

Page 11: ...ow for example the wiring of up to 64 DALI slaves directly via one bus line or two parallel bus lines using 2 connectors The module is supplied DC 18 V and common ground connections Warning The WAGO D...

Page 12: ...ing combination LonWorks Fieldbus Coupler 750 319 together with the WAGO TOPLON IF and PRIO Plug Ins The module is directly supported by the controllers of the WAGO I O SYSTEM 750 A higher level contr...

Page 13: ...VDE 0712 part 23 DSI Specification TRIDONIC ATCO Specification 2 0 Number of Slaves DALI 64 Number of Slaves DSI 100 Current output max 200 mA Voltage supply DALI DSI 18 V via DC DC converter 288 895...

Page 14: ...in the document Overview Approvals WAGO I O SYSTEM 750 which you can find on the CD ROM AUTOMATION Tools and Docs Item No 0888 0412 or in the internet under http www wago com Documentation WAGO I O SY...

Page 15: ...read out using the controller These functions blocks allow for both the Dali commands specified in the standard DIN IEC 60929 and the extended commands to be transmitted and executed Further informat...

Page 16: ...and Extended Commands 2 1 1 6 2 1Input Data Input data S D0 D1 D2 D3 D4 Status byte DALI response DALI address Message 3 Message 2 Message 1 The response of the Control Byte command is displayed in th...

Page 17: ...unction Command requests performed by toggling a bit An allocated bit in the status shows that the process is finished This bit takes the value of the request bit Control byte Bit 0 Bit 1 Bit 2 Bit 3...

Page 18: ...can be transmitted or received by the module 2 IR Init Request IA 0 Init Accepted Resetting the module into the default status The initialization is accomplished only with a rising edge The acknowledg...

Page 19: ...00 On and step up 9 15 0000 1XXX YAAA AAA1 0 0 0000 0000 Reserved 16 31 0001 XXXX YAAA AAA1 0 0 0000 0000 Go to scene 1 16 32 0010 0000 YAAA AAA1 0 0 0000 0000 Reset 33 0010 0001 YAAA AAA1 0 0 0000 00...

Page 20: ...y System Failure Level 165 1010 0101 YAAA AAA1 0 0 0000 0000 Query Fade Time Fade Rate 166 175 1010 XXXX YAAA AAA1 0 0 0000 0000 Reserved 176 191 1011 XXXX YAAA AAA1 0 0 0000 0000 Query Scene Level Sc...

Page 21: ...om Group 1 16 128 Store the DTR as Short Address 129 143 Reserved 144 Bit 0 0 OK Ballast Bit 1 0 OK Lamp Failure Bit 2 0 Off Lamp Power On Bit 3 0 Off Limit Error Bit 4 0 Terminate Fading Bit 5 0 No R...

Page 22: ...ade Rate 166 175 YAAA AAA1 Reserved 176 191 Lamp Power Level of the Scene XXXX as 8 Bit Number YAAA AAA1 Query Scene Level Scene 1 to 16 192 One bit for each Group LSB Group 0 0 is not associated to t...

Page 23: ...ess 1AAA AAA1 new Address 0x04 Replace Short Address 5 YAAA AAA1 1 255 0x05 Blink Show Address sec 6 0x06 Query Short Address available 0 31 7 0x07 Query Short Address available 32 63 8 0x08 Query Sta...

Page 24: ...ress 32 39 Address 40 47 Address 48 55 Address 56 63 Query State Ballast 32 63 0 OK 1 Error 10 Address 0 7 Address 8 15 Address 16 23 Address 24 31 Query Lamp Failure 0 31 0 OK 1 Error 11 Address 32 3...

Page 25: ...e initialized All search addresses used in the algorithm are sent back on the return channel message 3 5 When a short address is allocated the lamps assigned to this address are lighting When performi...

Page 26: ...ALI Address D2 Parameter 2 Duration of one flashing period resolution 600ms 300ms ON 300ms OFF 0x00 1 s default 0xFF Switching on one time D3 Parameter 1 Number of flashing sequences 1 0xFF 0x00 5 def...

Page 27: ...its of ballasts 41 up to 48 Return channel byte 4 Ballast error bits of ballasts 49 up to 56 Return channel byte 5 Ballast error bits of ballasts 57 up to 64 0x0A Query Lamp Failure 0 31 Request_Lamp_...

Page 28: ...ts of ballasts 41 up to 48 Return channel byte 4 PowerOn bits of ballasts 49 up to 56 Return channel byte 5 PowerOn bits of ballasts 57 up to 64 0x0E Setting DALI DSI Mode and Polling Set_Feature_Reg...

Page 29: ...xec Device Type Depending Commands 0x13 Response on QUERY ACTUAL LEVEL devices 56 to 59 Request_Level_56_59 Responses on QUERY ACTUAL LEVEL of the devices 56 to 59 Backward channel Byte 1 Level 56 Ini...

Page 30: ...rse function to 0x15 Backward channel Byte 4 contains the Level Poll Period in msec 2 30 ms 2540 ms 0xFF Off Default Backward channel Byte 3 contains the number of devices polled with QUERY ACTUAL LEV...

Page 31: ...C converter must be connected to ground using the appropriate FE connection S on the rail The length of the power supply cable between the DC DC converter and the module must not exceed 1 meter Both d...

Page 32: ...The minimum cross section of the conductors depends on the cable length Cable length Conductor cross section min 100 m 0 5 mm 100 m 150 m 0 75 mm 150 m 1 5 mm Attention The maximum voltage drop of the...

Page 33: ...the same time is made possible by broadcast addressing Using DALI up to 64 short addresses 16 group addresses and 16 scene light values can be defined Addresses assignement is done using the software...

Page 34: ...Fade rate System failure level Power on level The electronic ballasts are provided with a logarithmic dimming curve so that adaptation to the eye sensitivity can be achieved Emergency operation setti...

Page 35: ...750 641 DALI DSI Master Module 35 Notes WAGO I O SYSTEM 750 I O Modules...

Page 36: ...WAGO Kontakttechnik GmbH Co KG Postfach 2880 D 32385 Minden Hansastra e 27 D 32423 Minden Phone 05 71 8 87 0 Fax 05 71 8 87 1 69 E Mail info wago com Internet http www wago com...

Reviews: