20
•
750-641 [DALI/DSI Master Module]
Process
Data
WAGO-I/O-SYSTEM
750
I/O
Modules
Output Data
D0
D1
D2
D3
D4
No.
Command
Code
DALI
Address
=0
=0
=0
Function
149
1001 0101
YAAA AAA1
0
0
0000 0000 Query Reset State
150
1001 0110
YAAA AAA1
0
0
0000 0000 Query Missing Short Address
151
1001 0111
YAAA AAA1
0
0
0000 0000 Query Version Number
152
1001 1000
YAAA AAA1
0
0
0000 0000 Query Content DTR **)
153
1001 1001
YAAA AAA1
0
0
0000 0000 Query Deviec Type
154
1001 1010
YAAA AAA1
0
0
0000 0000 Query Physical Min – Level
155
1001 1011
YAAA AAA1
0
0
0000 0000 Query Power Failure
156–
159
1001 11XX
YAAA AAA1
0
0
0000 0000 Reserved
160
1010 0000
YAAA AAA1
0
0
0000 0000 Query Actual Level
161
1010 0001
YAAA AAA1
0
0
0000 0000 Query Max – Level
162
1010 0010
YAAA AAA1
0
0
0000 0000 Query Min – Level
163
1010 0011
YAAA AAA1
0
0
0000 0000 Query Power On – Level
164
1010 0100
YAAA AAA1
0
0
0000 0000 Query System Failure – Level
165
1010 0101
YAAA AAA1
0
0
0000 0000 Query Fade Time / Fade Rate
166–
175
1010 XXXX
YAAA AAA1
0
0
0000 0000 Reserved
176-
191
1011 XXXX
YAAA AAA1
0
0
0000 0000 Query Scene – Level (Scene 1 to 16)
192
1100 0000
YAAA AAA1
0
0
0000 0000 Query Groups 1 to 8
193
1100 0001
YAAA AAA1
0
0
0000 0000 Query Groups 9 to 16
194
1100 0010
YAAA AAA1
0
0
0000 0000 Query Random Address (H)
195
1100 0011
YAAA AAA1
0
0
0000 0000 Query Random Address (M)
196
1100 0100
YAAA AAA1
0
0
0000 0000 Query Random Address (L)
197–
223
110X XXXX
YAAA AAA1
0
0
0000 0000 Reserved
224–
255
11XX XXXX YAAA AAA1
0
0
0000 0000 Query Application Extended Commands
999
XXXX XXXX YAAA AAA0
0
0
0000 0000 WAGO specific:
Direct Lamp Power Control
*)
Attention
The configuration commands No. 32 to No. 128 must be sent in each case a second time before
the execution by the DALI master within the next 100 ms. Between the two commands no further
command may be sent to the same addressed electronic ballast.
**) DTR: Data Transfer Register
Response
Response
DALI-Code
‚Yes‘ 1111
1111
‚No‘ No
Answer
8-Bit Information
XXXX XXXX