112 Fieldbus Communication
WAGO-I/O-SYSTEM 750
750-306 DeviceNet
TM
Fieldbus Coupler
Manual
Version 2.0.0
Table 82: Instance 1
Attributes
ID
Utilization
in Device
Access
Rights
Name
Data Type Description
25
specific
get/set
BK_DO_FAU
LT_REACTIO
N_ON_RELE
ASE_COS
USINT
Defines the behavior after
allocation of the change of state
and cyclic
I/O connection
0: No activity (default)
1: Error behavior processing for
fieldbus coupler/controller
26
specific
get/set
BK_DO_FAU
LT_REACTIO
N_ON_RELE
ASE_ST
USINT
Defines the behavior after
allocation of the strobed
connection
0: No activity (default)
1: Error behavior processing for
fieldbus coupler/controller
40
specific
get/set
BK_static_anal
og_digital_inp
ut_mapping
UINT
Defines how the values for the
analog and digital input bits are
determined.
0000: All bits are digital.
0016: One word is analog, the
remaining bits are digital.
0032: Two words are analog, the
remaining bits are digital.
...
0xFFFF: All bits are handled as
“Module Type” (default).
41
specific
get/set
BK_static_anal
og_digital_inp
ut_mapping
UINT
Defines how the values for the
analog and digital outputs bits
are
determined.
0000: All bits are digital.
0016: One word is analog, the
remaining bits are digital.
0032: Two words are analog, the
remaining bits are digital.
...
0xFFFF: All bits are handled as
“Module Type” (default).
(If the number of analog bits
exceeds the size of the process
image, all bits are mapped to
analog bits.)
42
specific
get/set
BK_specific_c
oupler_
behavior
UINT
Defines the fieldbus
coupler/controller functionality.
0xFFFF: All possible functions
are enabled. (Resetting a bit to 0
disables the related function.)
It is only possible to reduce the
functionality. Resetting to “1” is
ignored.