22 Device Description
Compact Power
787-1200 Power supply
Manual
Version 1.0.0
3.5.2
Input
Table 9: Technical Data – AC Input
Parameter
Value
Input nominal voltage range
100 … 240 VAC
Input voltage range, max.
90 … 264 VAC
Input frequency
47 … 63 Hz
Input current
1)
< 0.27 A
< 0,27 A
Power factor
1)
> 0.5
> 0,5
1)
At nominal load
Table 10: Technical Data – Inrush Current
Parameter
Value
Inrush current
1)2)
230 VAC
< 30 A
1)
Cold start, at room temperature of 25 °C
2)
After 1 ms at nominal load
Table 11: Technical Data – Mains Failure Buffering Time
Parameter
Value
Mains failure buffering time,
typ.
1)
110 VAC
> 20 ms
230 VAC
> 100 ms
Holding time, typ.
1)
110 VAC
> 25 ms
230 VAC
> 100 ms
1)
At nominal load
Table 12: Technical Data – Input Side Connection
Property
Value
Connection Technology
Spring pressure connection technology
(
picoMAX
®
5.0, 2-pole)
Cross section
Solid
0.2 … 2.5 mm² / AWG 24 … 12
Fine-stranded
0.2 … 2.5 mm² / AWG 24 … 12
Insulated ferrule
0.25 … 1.5 mm² / AWG 23 … 16
Uninsulated Ferrule 0.25 … 2.5 mm² / AWG 23 … 10
Strip length
9 … 10 mm / 0.35 … 0.39 in
Required tools (conductor termination) Operating tool, Type 2 (see Section
“Accessories”)