![WAGO 765-1205/100-000 Product Manual Download Page 76](http://html1.mh-extra.com/html/wago/765-1205-100-000/765-1205-100-000_product-manual_3301094076.webp)
765-1205/100-000
Commissioning
76
Product manual | Version: 2.0.0
8DIO FLD EC DC 24V 2.0A
For entering these, there are two checkboxes in the table for each pin of a port:
force
for
switching the forcing functionality on/off, and
set/clr
for setting or deleting the setpoint
(1 bit); the latter checkbox is only relevant if the
force
box is checked. The following ap-
plies to this:
• All inputs for input simulation are entered in the right half of the table under “Input
process data”; all the inputs for output forcing are then entered in the left half of the ta-
ble under “Output process data.”
You can find a description of and more information on the forcing function and explana-
tions of terms under
8
.
Each of the eight ports (X01 ... X08) has its own table row.
• For pin 4, there is always the option of forcing. Whether forcing is also possible for pin
2 depends on the current configuration of pin 2. Pin 2 must be configured as a digital
input to force the input process data and as a digital output to force the output process
data.
This determines whether or not the pin 2 checkboxes are editable, and
Pin 2
or
No pin
2
is used as the column title in the screen form.
Concurrent Access
As long as one user is accessing the forcing functionality through a forcing medium, e.g.,
the WAGO I/O Field Webserver, it is locked for all other users of the module. They cannot
access the forcing functionality until the user that is active now terminates his or her ac-
cess.
In this case, the Web browser displays a message box with the text
“Somebody else
is already forcing. Try again later.”
When the forcing functionality is being
accessed, a small orange icon also appears in the forcing option entry in the menu bar on
the left.
10.3.2 WAGO I/O Field app
10.3.2.1 Parameterizing a Module with the WAGO I/O Field App
Note
Read the online help!
You can find Product-specific information on the WAGO App I/O Field in the online help
for the app.
10.3.3 OPC UA Server
The device has an OPC UA server. An OPC UA client can establish a connection with the
device and access the following parameters, among others:
• Device identification
• Configuration parameters
• Process Data
• Measured values
• Diagnostic information
• Statistical information