765-1205/100-000
Planning
Product manual | Version: 2.0.0
41
8DIO FLD EC DC 24V 2.0A
6.3 Settings Options
6.3.1 Module Parameters
Indexes 0x2000 to 0x2003
Parameters with indexes 0x2000 to 0x2003 configure the module.
Table 33: Module Parameters
Index
Subindex
Value Range
Value Range
Default
Description
0x2000.0
0
Force mode setting
0: Force mode en-
able
0
The “Forcing” operating mode may be
used.
1: Force mode dis-
able
The “Forcing” operating mode must not be
used.
0x2001.0
0
PD layout configura-
tion
0: port-based
0
Order of the process data of the digital in-
puts and digital outputs:
Bit 0 = port X01 pin 4, bit 1 = port X01
pin 2,
bit 2 = port X02 pin 4, bit 3 = port X02
pin 2, ...
1: pin-based
Order of the process data of the digital in-
puts and digital outputs:
Bit 0 = port X01 pin 4, Bit 1 = port X02
pin 4,
bit 2 = port X03 pin 4, bit 3 = port X04 pin 4,
...
bit 8 = port X01 pin 2, bit 9 = port X02
pin 2, ...
0x2002.0
1
DO substitue mode
0: Set to low
0
Set all digital outputs to low level in the
event of error
1: Use substitute val-
ues
Set digital outputs to a pre-defined substi-
tute value in the event of error.
If this setting is used, the value of the “DO
substitute value” parameter determines the
substitute value.
2: hold last
Hold digital outputs at their last value in the
event of error
0x2002.0
2
DO substitue value
0 … 65535
0
Substitute value for the digital outputs if the
“Use substitute values” setting is used. The
input depends on the “PD layout configura-
tion” parameter.
Use a binary-to-decimal converter to calcu-
late this value.
0x2003.0
1
Disable BT
0: Activation of BT in-
terface is allowed
0
The Bluetooth
®
interface can be enabled by
an optical signal of a mobile device and in
connection with the WAGO I/O Field app.
1: Disable activation
of BT interface
The Bluetooth
®
interface cannot be enabled
by an optical signal of a mobile device and
in connection with the WAGO I/O Field app.