765-1205/0100-0000
Diagnostics
Product manual | Version: 1.0.0
87
8DIO FLD EC DC 24V 2.0A
Emergency Error Code (hex)
Description
22xx
Current inside the device
23xx
Current, device output side
30xx
Voltage
31xx
Mains Voltage
32xx
Voltage inside the device
33xx
Output Voltage
40xx
Temperature
41xx
Ambient Temperature
42xx
Device Temperature
50xx
Device Hardware
60xx
Device Software
61xx
Internal Software
62xx
User Softwares
63xx
Data Set
70xx
Additional Module
80xx
Monitoring
81xx
Communication
8110
CAN Overrun (Objects lost)
8120
CAN in Error Passive Mode
8130
Life Guard Error or Heartbeat Error
8140
recovered from bus off
8150
Transmit COB-ID
82xx
Protocol Error
8210
PDO not processed due to length error
8220
PDO length exceeded
90xx
External Error
F0xx
Additional Functions
FFxx
Device-specific
The following device-specific emergency error codes are used by the device (diagnostic
type: warning):
Table 69: General Alarms
Emergency
Error Code
(hex)
Alarm
Description
Remedy
0xFF00
Undervoltage
Undervoltage in supply line 1L
The supply line has fallen below the limiting
value for the minimum voltage.
Check supply voltage
0xFF01
Overvoltage
Overvoltage in supply line 1L
The supply line has exceeded the limiting
value for the maximum voltage.
Check supply voltage
0xFF02
Overtempera-
ture
Overtemperature
The device temperature has exceeded the
upper limiting value.
Eliminate external heat source
or overload.
0xFF03
Overload
Overload in supply line 1L
The total current in supply line 1L has ex-
ceeded the upper limiting value.
Eliminate overload.
0xFF04
Overload, 2L
Overload in supply line 2L