WAGO-TO-PASS® 761
Connect Devices
33
761-210 Telecontrol Module Compact
Manual
Version 2.0.0
5
Connect Devices
5.1
Connecting the Push-wire Connections to the
Conductor
The push-wire connections of the
TO-PASS
®
telecontrol modules are designed for
solid or fine-stranded conductors with cross sections between 0.5 … 1.5 mm²
(AWG 22 … 14 „sol“).
Connect only one conductor per clamp!
Only connect one conductor to each push-wire connection. Do not connect more
than one conductor at one single connection!
If more than one conductor must be routed to one connection, these must be
connected in an up-circuit wiring assembly, for example using WAGO feed-
through terminals.
Terminate both solid and ferruled conductors without actuation by simply pushing
them in. For all other conductor types, a suitable operating tool must be used to
open the push-wire connection for connection.
Observe strip length!
When using short ferrules, the retention force of the push-wire connection may be
reduced. Strip length from 9 to 10 mm must be observed for a safe push-wire
connection.
1.
To open the push-wire connection, use the tool to press the button above the
connection.
2.
Insert the conductor into the corresponding connection opening.
3.
To close the push-wire connection, release the button. The conductor is
clamped.