Commissioning
WAGO-TO-PASS® 761
761-210 Telecontrol Module Compact
Manual
Version 2.0.0
Table 22: Configuring of digital inputs
Alarm settings
First value
Check this box to have a message sent when the first limit is
exceeded for upward counting or when the first lower limit is
violated for downward counting.
In the field provided, enter the first limit for which a message
is to be sent when this limit is violated (upper/lower limit)
(see below).
The check box and the input field are active only when the
input is used as a counter input.
Activation text
In this field enter the text to be contained in the message
transmitted when the digital input has been set, or when the
counted value has violated the first limit.
Address
Use this button to select the addresses to which the message
is to be transmitted when the digital input has been set, or
when the counted value has violated the first limit.
Click the button
[Internet]
for applications with GPRS
transmission.
Analog value
Use these buttons to select up to four analog values which
can also be transmitted with the message when the digital
input has been set, or when the counted value has violated the
first limit.
Delay time
In these fields select the time (in hours, minutes and seconds)
by which the message is to be delayed after setting of the
digital input.
If the input is reset before the defined delay period elapses,
no activation/deactivation message will be sent.
Enter "00:00:00" in this field to deactivate this function. The
message will then be sent immediately.
This function is available starting with Firmware Version FW
2.33.
The selection fields are active only when the input is used as
a digital input.
Second value
Check this box to have a message sent when the second limit
is exceeded for upward counting or when the second lower
limit is violated for downward counting.
In the field provided, enter the second limit for which a
message is to be sent when this limit is violated (upper/lower
limit) (see below).
The check box and the input field are active only when the
input is used as a counter input.