Fieldbus Communication
•
193
EtherNet/IP (Ethernet/Industrial Protocol)
WAGO-I/O-SYSTEM 750
ETHERNET TCP/IP
4.3.3.2.12
Discrete Output Point (66
hex
)
Class
Attribute ID Access
Name
Data type Description
Default
value
1
Get
Revision
UINT
Revision of this object
1 (0x0001)
2
Get
Max Instance
UINT
Max. number of instances
-
Instance 1..255 (1. to 255. Digital Output Value)
Attribute ID Access
Name
Data type Description
Default
value
1 Get
DopObj_Value
BYTE
Digital output (only Bit 0 is
valid)
-
Common Services
Service available
Service code
Class Instance
Service
Name
Description
0E hex
yes
yes
Get_Attribute_
Single
Supplies contents of the appropriate attribute
10 hex
no
yes
Set_Attribute_
Single
Modifies an attribute value
4.3.3.2.13
Analog Input Point (67
hex
)
Class
Attribute ID Access
Name
Data type Description
Default
value
1
Get
Revision
UINT
Revision of this object
1 (0x0001)
2
Get
Max Instance
UINT
Max. number of instances
-
Instance 1..255 (1. to 255. Analog input value)
Attribute ID Access
Name
Data type Description
Default
value
1
Get
AipObj_Value
Array of Byte
Analog input
-
2 Get
AipObj_Value_Lengt
h
USINT
Length of the input data
AipObj_Value (in byte)
-
Common Services
Service available
Service code
Class Instance
Service
Name
Description
0E hex
yes
yes
Get_Attribute_
Single
Supplies contents of the appropriate attribute