WAGO I/O SYSTEM 750 XTR
Use in Hazardous Environments
45
750-610/040-000 Power Supply 24 VDC Fuse Diagn XTR
Manual
Version 2.0.0
Table 22: Description of Marking Example According to ATEX and IECEx
Marking
Description
TUEV 07 ATEX 554086 X
IECEx TUN 09.0001 X
Approving authority resp. certificate numbers
Dust
II
Equipment group: All except mining
3 D
Category 3 (Zone 22)
Ex
Explosion protection mark
tc
Type of protection: Protection by enclosure
IIIC
Explosion group of dust
T135°C
Max. surface temperature of the enclosure
(without a dust layer)
Dc
Equipment protection level (EPL)
Mining
I
Equipment group: Mining
M2
Category: High level of protection
Ex
Explosion protection mark
d
Type of protection: Flameproof enclosure
I
Explosion group for electrical equipment for
mines susceptible to firedamp
Mb
Equipment protection level (EPL)
Gases
II
Equipment group: All except mining
3 G
Category 3 (Zone 2)
Ex
Explosion protection mark
nA
Type of protection: Non-sparking equipment
IIC
Explosion group of gas and vapours
T4
Temperature class: Max. surface temperature
135 °C
Gc
Equipment protection level (EPL)