66 Commissioning
WAGO-I/O-SYSTEM 750
750-564 4AO U/I
Manual
Version 1.0.0
Table 51: “Common” Menu Item
Parameter
Value
Description
K-Bus timeout
Post-Delay [ms]
[16-bit decimal
value]
If the I/O module watchdog is triggered
(e.g., in the event of a faulty local bus
connection), the outputs of the individual
channels switch to a defined output state
(see section “Channel Settings”). If the
error is eliminated, the I/O module waits for
the amount of time specified here before a
change to the output channels occurs. This
prevents output value jumps when the local
bus restarts.
[Input field]
0…600
*)
…65535
*)
Factory setting
7.1.3.2 Channel Settings
Figure 20: Menu Items “Channel 1” ... “Channel 4”
Menu items
[Channel 1]
to
[Channel 4]
contain the channel-specific parameters
of the I/O module. The parameter list is identical for all channels. If you change a
value, a pen symbol appears to the left of the parameter in question, and the
[Write]
button, which had been grayed out before, is enabled.
Click the
[Write]
button to save any settings you have been made and apply
them to the I/O module.