750-563 [2 AO 0/4-20mA / 6-18V DC 16 Bit] • 47
Fieldbus-Specific
Behavior
WAGO-I/O-SYSTEM 750
I/O Modules
2.1.1.11 Fieldbus-Specific Behavior
2.1.1.11.1 Default
Mapping
Byte
Input data
Output data
0
S0
Status byte 0
C0
Control byte 0
1
D0
Not used
D0
Output data word 1 (LSB)
2
D1
Not used
D1
Output data word 1 (MSB)
3
S1
Status byte 1
C1
Control byte 1
4
D2
Not used
D2
Output data word 2 (LSB)
5
D3
Not used
D3
Output data word 2 (MSB)
2.1.1.11.2 Mapping for Couplers/Controllers with Word-Alignment
Valid for: 750-841, 750-842
Byte
Input data
Output data
0
S0
Status byte 0
C0
Control byte 0
1
---
Fill byte for word alignment
---
Fill byte for word alignment
2
D0
Not used
D0
Output data word 1 (LSB)
3
D1
Not used
D1
Output data word 1 (MSB)
4
S1
Status byte 1
C1
Control byte 1
5
---
Fill byte for word alignment
---
Fill byte for word alignment
6
D2
Not used
D2
Output data word 2 (LSB)
7
D3
Not used
D3
Output data word 2 (MSB)