2.1.1.9.4.4 Examples
Example 1: Writing
The value 2300 (dec.) should be written to parameter channel address 8
(corresponds to register 36, offset user calibration, channel 1).
1. Enter the value 2300 in register 56
2. Enter the following in register 57: Bit15 = 1, Bit 14 = 1, Bit 7-0 = 0000
1000
Example 2: Reading
The value should be read from the parameter channel address 15 (corresponds
to register 42, overrange, channel 2):
1. Enter the following in register 57: Bit15 = 0, Bit 14 = 0, Bit 7-0 = 0000
1111