750-563 [2 AO 0/4-20mA / 6-18V DC 16 Bit] • 39
Parameter
Setting
WAGO-I/O-SYSTEM 750
I/O Modules
The following parameters can be changed and loaded onto the module.
Description
Input/Selection
Description
0 ... 20 mA
4 ... 20 mA*
Operation Mode
(0)6 ... 18 V
Selection of the operating mode of
the device
0 … +65535*
-32768 … +32767 (Two´s
complement)
Number Format
-32768 … +32767 (Sign-and-
magnitude)
Setting of the numeric display
Output process value*
Output
Output high-impedance
Setting of the switch-on behavior
0 ms
100 ms
200 ms
300 ms
500 ms*
750 ms
1 sec
Power-On Delay After
Excess Temperature
Shutdown
2 sec
Setting of the switch-on delay
Off*
Keep Limit Values
On
Setting of the overrun limitation
Lower Limit Value
0* ... +65535
Setting of the lower limit value
underrange limit (UNR)
Upper Limit Value
0 ... +65535*
Setting of the upper limit value
overrange limit (OVR)
Keep last output value
Behavior of the RUN LEDs on I/O
module timeout
RUN LED is always lit
K-Bus Timeout
Behaviour
Execute the function below*
Behavior of the RUN LEDs on I/O
module timeout
RUN LED goes out after 100 ms
Output 0 V / 0 A*
Keep last value
Output high-impedance
Behavior after I/O module timeout
User power-on value
Action at Timeout
WAGO power-on value
Substitute value after I/O module
timeout