WAGO-I/O-SYSTEM 750
Description of Operation
69
750-484 2 AI 4-20 mA HART Ex i
Manual
V 1.2.0 HW-Version 04, SW-Version 03
Figure 27: Example of a FDT/DTM Communication via PROFIBUS
10.3.2 Commissioning on a 750-333, -833 via FDT/DTM
This section describes the most important steps for commissioning the HART I/O
module on a PROFIBUS DP/V1 Fieldbus Coupler 750-333 or Controller 750-833
using FDT/DTM.
Along with the installed and wired fieldbus node hardware, which includes the
PROFIBUS DP/V1 Fieldbus Coupler 750-333 or Controller 750-833, it is
necessary to install the following software before carrying out the operations
described.
Table 41: Software Required for the Commissioning on a 750-333, -833 via FDT/DTM
Pos.
Name
Description
Item-No.:
1
WAGO-I/O-
CHECK
(optional)
Commissioning tool for
the WAGO-I/O-SYSTEM
750
759-302
2
GSD files for PROFIBUS
with installation program /
Series 750, 752 and 755
Fieldbus-specific software
(e.g., GSD files for
PROFIBUS)
750-910
Download:
www.wago.com
3
WAGO
frame
FDT frame application for
parameterization,
commissioning and
diagnostics of devices with
DTM device drivers
759-370
4
WAGO_Profibus_HART_
DTM 759-360
DTM for PROFIBUS
759-360
Both Download:
www.wago.com
5
WAGO_075x-08xx_DTM DTM for the 75x-8xx
controller
Obtainable from
HART field
device
manufacturers
6
HART device DTM(e.g.,
Generic HART DTM from
ICS GmbH)
DTM for parameterization,
commissioning and
diagnostics of HART-
enabled field devices
1.
As is typical for a PROFIBUS application, set up the operating mode “2 AI
+ acyclic PROFIBUS services” using the GSD files. You will find more
detailed information on this in the section “Operating Modes“
> … > “Setting Up via GSD”.
Alternatively you can also open WAGO-I/O-
CHECK
if available. In this
case, proceed as described in the section “Operating Modes Parameters”
> … > “Setting Up using WAGO-I/O-
CHECK
”.