16 - 4PU & 4PS - Wago
6.6.1 Password
The button setting function can be protected by setting a password. This password is also valid for settings via Blue- tooth.
The default password is 0000. This password can only be changed using the button function.
6.6.2 Tariff
The default tariff is 1. The tariff can be set to T2, T3 and T4. Tariff 1 and 2 are always displayed in part 1 and 2 of the meters.
kWh values in tariff 3 and 4 will be added to the automatic scroll in part 2 of the display.
6.6.3 S0-Impulsausgang
The energy meter is equipped with two pulse outputs (forward & reverse or active & reactive) which are optically isolated from
the inside circuit. It generates pulses in proportion to the measured consumption for purpose of remote reading or accuracy testing.
The pulse output is a polarity dependent, open-collector transistor output requiring an external voltage source for correct
operation. For this external voltage source, the voltage (Ui) should be lower than 27V DC. The maximum switching current (Imax)
is 100mA. To connect the impulse output, connect 5-27V DC to connector 4/6 (collector), and the signal wire (S) to connector 5
(emitter).
Beispiel Verdrahtung der S0-Impulskontakte