24 Device Description
WAGO-I/O-SYSTEM 750 XTR
750-407/040-000 2DI 220V DC 3.0ms XTR
Manual
Version 1.3.0
3.6.5
Connection Type
Table 11: Technical Data – Field Wiring
Wire connection
CAGE CLAMP
®
Cross section
0.25 mm² … 2.5 mm² / AWG 24 … 14
Stripped lengths
8 mm … 9 mm / 0.33 in
Table 12: Technical Data – Power Jumper Contacts
Power jumper contacts
Blade/spring contact, self-cleaning, hard
gold plated (except FE)
Table 13: Technical Data – Data Contacts
Data contacts
Slide contact, self-cleaning, hard gold
plated
Pos: 42.5 /Serie 750 (WAGO-I/O-SYST EM)/Ger ätebeschrei bung (alte Str uktur)/Technische Daten/VS (Variabl ensteuerung)/Technische Daten M echanische Bedi ngungen (VS) - XTR @ 15\mod_1369387569701_21.docx @ 120364 @ 3 @ 1
3.6.6
Mechanical Conditions
Table 14: Technical Data – Mechanical Conditions
Vibration resistance
Max. 5g
*
*
Follow the installation instructions
Pos: 42.6 /Serie 750 (WAGO-I/O-SYST EM)/Ger ätebeschrei bung (alte Str uktur)/Technische Daten/VS (Variabl ensteuerung)/Technische Daten kli matische U mwel tbedi ngungen (VS) - XTR @ 15\mod_1369387559187_21.docx @ 120360 @ 3 @ 1
3.6.7
Climatic Environmental Conditions
Table 15
: Technical Data ‒ Climatic Environmental Conditions
Surrounding air temperature, operation
−40 °C … +70 °C
Surrounding air temperature, storage
−40 °C … +85 °C
Relative humidity
*)
95 %
Elevation above sea level
without temperature derating
with temperature derating
max.
0 m … 2000 m
2000 m … 5000 m: 0.5 K per 100 m
5000 m
Resistance to harmful substances
Acc. to IEC 60068-2-42 and
IEC 60068-2-43
Maximum pollutant concentration at
relative humidity < 75 %
SO
2
≤
25 ppm
H
2
S
≤
10 ppm
*)
Short-term condensation acc. class 3K7 / IEC EN 60721-3-3 permitted, applying
E-DIN 40046-721-3 (except wind-driven precipitation, water and ice formation)
Pos: 43 /D okumentation allgemei n/Glieder ungselemente/---Seitenwechsel--- @ 3\mod_1221108045078_0.docx @ 21810 @ @ 1