![Waeco AirConServiceCenter ASC 3500 G LE Operating Manual Download Page 113](http://html1.mh-extra.com/html/waeco/airconservicecenter-asc-3500-g-le/airconservicecenter-asc-3500-g-le_operating-manual_3121774113.webp)
EN
113
ASC2500G/ASC3500G
Troubleshooting
11
Troubleshooting
Problem
Cause
Remedy
The display shows
“
Warning!
Internal vessel overpres-
sure!
”
Normal message that
appears during the recycling
process.
To continue, press
ENTER
for three seconds.
If this message appears
repeatedly, notify customer
services.
The display shows
“
Warning!
Internal tank is full!
”
The internal refrigerant con-
tainer is too full to hold the
quantity to be extracted.
Drain the internal refrigerant
container in the proper man-
ner.
The display shows
“
Warning!
Pressure inside the A/C
system.
Recovery start!
”
Normal message that
appears at the start of the
vacuum process. There is
still pressure present in the
air conditioning system.
No action is required. The
process continues automati-
cally.
The display shows
“
Warning!
Pressure inside the A/C
system
”
Message during the vacuum
process. There is pressure in
the air conditioning system.
No action is required. The
process continues automati-
cally.
The display shows
“
Not enough vacuum!
Carry on?
”
Message that appears during
the vacuum process if the
pressure in the air condition-
ing system after 8°minutes is
still more than 50°mbar.
Check the air conditioning
system or the connections
between it and the
AirConServiceCenter for
leaks.
The display shows
„
A/C system leakage!
Carry on?
“
Message at the end of the
vacuum process. The air
conditioning system shows a
vacuum loss of more than
120°mbar during the check-
ing time.
Check the air conditioning
system or the connections
between it and the
AirConServiceCenter for
leaks.
The display shows
“
Drained oil glass empty-
ing!
”
This message appears dur-
ing the extraction or recycling
process if there is more than
150°ml of used oil in the con-
tainer.
Dispose of the content of the
used oil container in an envi-
ronmentally responsible
manner.
The display shows
“
Warning!
Not enough vacuum for
injection!
”
Message that appears during
the filling phase if the vac-
uum in the air conditioning
system is insufficient to end
the process.
Check the air conditioning
system or the connections
between it and the
AirConServiceCenter for
leaks.
The display shows
“
Quantity too large.
Fill internal vessel!
”
This message appears dur-
ing the filling process if there
is not enough refrigerant in
the internal container to finish
the process.
Fill the refrigerant container.
Summary of Contents for AirConServiceCenter ASC 3500 G LE
Page 2: ......
Page 242: ...RU ASC2500G ASC3500G 242 1 2 A I ENTER Short selection 1 2 3 1 2 3 1 248 249 8 A E...
Page 245: ...RU 245 ASC2500G ASC3500G 2 2 AirConServiceCenter 230 50 2 3...
Page 255: ...RU 255 ASC2500G ASC3500G 7 7 1 21 18 19 20 2 21 3 256 20 19 18 21...
Page 263: ...RU 263 ASC2500G ASC3500G I 8 2 2 1 STOP ENTER USER CODE WRONG CODE Max Mustermann...
Page 280: ...RU ASC2500G ASC3500G 280 5 21 18 19 20 ENTER 6 18 20 19 21 7 STOP 20 19 18 21...
Page 290: ...RU ASC2500G ASC3500G 290 9 9 USB USB I AirConServiceCenter 1 USB 2 USB USB 16 USB FAT32 16...
Page 292: ...RU ASC2500G ASC3500G 292 9 10 I 20 6 1 21 20 2 M N 6 20 21 M N...
Page 293: ...RU 293 ASC2500G ASC3500G 3 O P 4 N Q 5 9 11 11 12 13 14 AirConServiceCenter P O Q N...
Page 294: ...RU ASC2500G ASC3500G 294 10 10 1 I 10 2 10 3 AirConServiceCenter M...
Page 297: ...RU 297 ASC2500G ASC3500G Error 01 Error 02 Error 03 Error 04 Error 09 Error 10 Error 12 10 C...
Page 298: ...RU ASC2500G ASC3500G 298 Error 52 USB USB USB FAT32 Error 60 Error 61...