wc_tx004154gb_FM10.fm
41
HDR 115
Burner Setup
6.2
Setting up the Burner
Factory
settings
6.3
Checking and Adjusting the Electrodes
Requirements
■
Machine shut down
■
Power disconnected
■
Burner cool
When to
inspect
Check electrode alignment after each nozzle change.
Procedure
Perform the procedure below to inspect or adjust the electrodes.
1. Remove the burner assembly. See topic
Removing and Installing the Burner.
2. Inspect the condition of the electrode tips
(a)
. Replace any damaged or worn
electrodes.
3. Verify the electrode gap is set to the recommended measurement.
Refer to the table below to determine the condition of the electrode tips. Replace
electrodes if tips become rounded.
Machine
Nozzle size
Fuel pressure
Air damper
psi
bar
HDR 115
0.65 (80ºW) gph
166
11.4
0.126 in. (3.2 mm)
Condition
Task
None; ok as is
None; ok as is
Replace
2–3 mm
0.08–0.11 in.
wc_gr013177
6–8 mm
0.23–0.31 in.
3–4 mm
0.11–0.15 in.
C L
a