Operation
GPi 3200 / 4300
34
wc_tx001239gb.fm
2.17
Using AC Power
Prerequisites
Verify that the engine is operating.
Verify that the voltage displayed on the LCD
(j)
is approximately 120V.
Turn off the equipment to be connected to the generator.
Confirm that the equipment to be connected to the generator does not exceed
the maximum rated power output and specifed amperage.
Engine switch
position
Leave the engine switch
(h)
in the RUN position while the machine is operating.
Connecting
equipment
1. Insert the equipment plug into the 20A GFI receptacle
(b)
or the 30A twist-lock
receptacle
(c)
.
Note: To use the 30A twist-lock receptacle, insert the plug into the receptacle and
turn it clockwise to the LOCK position.
2. Turn on the power switch for the equipment.
Overload fault
Excessive current draw on the generator will cause an overload fault. When this
fault occurs, AC power is cut off and
O_Lod
displays on the LCD.
To clear an overload fault, stop the engine immediately and remedy the overload
condition. Then re-start the engine.
Circuit
breaker
activation
If equipped, your machine’s circuit breakers
(r)
shut off the electrical current when the
current exceeds its limit. Circuit breakers also activate if a malfunction occurs in a
piece of equipment connected to the generator.
Reset circuit breakers by returning the toggle switches to the ON position.
Stop the machine and identify the cause if a circuit breaker activates repeatedly.
Disconnecting
equipment
1. Turn off the power switch for the equipment.
2. Remove the plug from the 20A GFI receptacle or the 30A twist-lock receptacle.
Note: To remove the plug from the 30A twist-lock receptacle, first turn the plug
counter-clockwise to unlock it.
WARNING
Electric shock hazard. Failure to properly ground the generator could lead to
electrical sparks, especially if the connected electrical equipment is grounded.
f
Make sure the generator is properly grounded. See
Grounding the Generator
.
wc_gr006667
AC 120V
AC 120V
NEUTRAL BONDED TO FRAME
NEUTRAL BONDED TO FRAME
RESET
RESET
TEST
TEST
OFF
OFF
OFF
OFF
TOTAL 2.8kVA
TOTAL 2.8kVA
NEUTRE MIS A LA MASSE
NEUTRE MIS A LA MASSE
A LA CARCASSE DU MOTEUR
A LA CARCASSE DU MOTEUR
b
r
h
c
j