For the calibration procedure refer to the following table:
Press
Eff ect
Do
1
FNC
Exit parameters
confi guration. Display
2 shows the writing
Latc.
Place the sensor on the
minimum functioning
value (associated with
Lo.L.i.
)
2
Set the value to minimum.
The display shows
Low
Place the sensor on the
maximum functioning
position
(associated with
up.L.i.
)
3
Set the value to
maximum.
The display shows
HiGt
To exit standard
procedure press
FNC
.
For
“virtual zero”
settings place the sensor
on zero point.
4
SET
Set the virtual zero
value. The display shows
uirt.
NB
: for selection
of
u.0in.
the procedure
on point 4 should
be followed at each
re-activation.
To exit the procedure
press
FNC
.
Max
Min
Zero