84
UR3274U - User manual
7.7
Pre-Programmed Cycle
Pre-programmed cycle function activates by setting
pr.cY.
on
parameter 48
op.Mo.
Controller reaches setpoint1 basing on the gradient set
on parameter 51
Grad.
, then it reaches max. power up
to setpoint2. When the process reaches max. power, this
setpoint is maintained for the time set on parameter 52
ma.t.i.
At expiry, process will reach ambient temperature according
to gradient entered on parameter 64
fa.Gr.
, then command
output will be disabled and display will visualize
Stop
.
Setpoin
t
Time
Setpoint 1
Setpoint 2
Maintenance time
Cooling
Max Power
Rising gradient
Cycle starts at each activation of the controller, or via
digital input if it is enabled for this type of functioning (see
parameter 50
dGt.i.
).
7.8
Programming module (optional)
Parameters and setpoint values can be duplicated from one
controller to another using the Programming module.
There are two methods:
• With the controller connected to the power supply
Insert the programming module
when the controller is off
.
On activation display 1 shows
memo
and display 2
show
----
(
Only if the correct values are saved in the
programming module
). By pressing the
key display 2