Retain these instructions for future service and adjustments
44 Harbor Park Drive, Port Washington, NY 11050
Tel: (800) 526-2588 Fax (800) 526-2585
www.waclighting.com
INSTRUCTIONS
Class II Electronic Transformer
Model EN-12300-RB2
CAUTION – TO REDUCE RISK OF FIRE AND ELECTRICAL SHOCK
Always turn off power at main switch prior to installation.
Intended for installation by a qualified electrician.
System is intended for installation in accordance with National Electric Code, and local
regulations. Consult with local inspector to assure compliance.
MAX LOAD
5 X 60W
MIN LOAD
1 X 20W
INPUT VOLTAGE
120V
INPUT CURRENT
2.5A
OUTPUT VOLTAGE
11.6V
CASE TEMP
85ºC (185
F)
AMBIENT TEMP
-20ºC TO 50ºC (-4
F TO 122
F)
FEATURES:
Electronic short circuit protection with auto-reset.
Overload protection with auto-reset.
Automatic thermal regulation.
Soft start delay to preserve bulb life, for use with tungsten filament lamps.
INSTALLATION
1. Use a minimum of #18 AWG for the output wire.
2. Transformers must be installed away from heat sources and accessible for service.
3. Connect building wires to like color transformer wires with wire nuts. Building ground
wire may be green or un-insulated, and attaches to green wire from transformer box.
4.
Connect fixture wires to pairs of output wires from
the transformer.
5.
Each wire pair represents is a 60-watt circuit.
6.
Wires to fixtures may be chain wired or “ home run” wired back to the transformer.
7.
Note: Heavy gauge wires introduce more electrical resistance to the line, which acts as
an additional load to the transformer. If using 14 or 12 gauge wire do not use the
maximum 60 watt load.
8.
High frequency output is only readable with a true RMS meter, with sufficient range
capability.
MAXIMUM LENGTH / VOLTAGE DROP GUIDELINE
WIRE SIZE
20 WATT
40 WATT
60 WATT
18 GAUGE
9 FT
8 FT
6 FT
16 GAUGE
14 FT
13 FT
11 FT
14 GAUGE
21 FT
19 FT
15 FT
12 GAUGE
28 FT
25 FT
21 FT