background image

 

13 

 

Note – motor size and speed settings of the device delivered with the VTS AHU are prepared by the manufacturer for 
optimal operation and should not be changed. 

 

DIP1 

DIP2 

Stepper motor = 2Nm 

OFF 

OFF 

Stepper motor = 4Nm 

ON 

OFF 

Stepper motor = 8Nm 

OFF 

ON 

Table 6 Stepper motor size setting 

 

DIP3 

DIP4 

Max RPM = 250 

OFF 

OFF 

Max RPM = 200 

ON 

OFF 

Max RPM = 170 

OFF 

ON 

Max RPM = 150 

ON 

ON 

Table 7 Max RPM settings 

3.3.3 LED Indicator 

The driver is fitted with a LED indicator - see Figure 19. The LED diode can be seen with both open and closed cover. 

 

Figure 19 LED indicator 

The statuses of the indicator are shown in Table 8 below. Note: Flashing means that the LED is off for 100 ms and on 
for min. 100 ms (ms=milliseconds). 

LED 

State 

OFF 

No voltage 

Green ON 

Voltage is present 

Flashing green 

Valid Modbus communication 

Red ON 

Rotor stopped due to critical alarm 

Flashing red 

Operating with reduced power 

Orange ON 

Test function activated 

Flashing orange 

Purging function activated 

Table 8 LED indicator statuses 

 

 

 

 

 

 

Summary of Contents for 7-1-0002-0083

Page 1: ...version 1 2 01 2022 ENERGY RECOVERY WHEEL MOTOR MANUAL OPERATION AND MAINTANANCE...

Page 2: ...ERAL SAFETY 3 2 PRODUCT DESCRIPTION TECHNICAL SPECIFICATION 3 3 INSTALLATION 6 3 1 Assembly and installation 6 3 2 Connection and wiring 7 3 2 1 Main voltage and stepper motor wiring 10 3 2 2 Cable re...

Page 3: ...ruction carefully Follow the connection diagrams to perform successful installation 2 PRODUCT DESCRIPTION TECHNICAL SPECIFICATION Rotary Heat Exchangers may be equipped with three different stepper mo...

Page 4: ...260 W Weight 2 4 kg 3 5 kg 5 0 kg Sealing grade IP 54 54 54 Operating temperature 40 C to 40 C 40 C to 40 C 40 C to 40 C Storage temperature 40 C to 70 C 40 C to 70 C 40 C to 70 C Dimensions 85 x 85 x...

Page 5: ...Figure 2 Stepper Motor 4 0 Nm all dimensions are given in mm units Figure 3 Stepper Motor 8 0 Nm all dimensions are given in mm units Figure 4 Dedicated controller all dimensions are given in mm unit...

Page 6: ...of the exchanger and most importantly the risk of motor damage as well as electric shock due to incorrect connection Warning Incorrect mechanical installation of the motor can be a cause of error aler...

Page 7: ...n the motor wait at least 5 minutes after disconnecting from the power supply Notes on proper installation Use fuses at power line Check the wires condition before operating Make sure that there are n...

Page 8: ...represents the cable connection with proper wiring description Figure 9 Extension cable Stepper motors are operated via designated controller connected with the motor by the up mentioned cables Figur...

Page 9: ...attempt to perform any repairs by your own Manufacturer warranty will not be void until the cover has traces of opening Controller is equipped with spring terminals to make the installation faster Sp...

Page 10: ...ble of the power supply should be connected on the terminals marked with letters L N and PE see Figure 15 Cables should be inserted via dedicated cable entries glands After the wiring is performed rem...

Page 11: ...11 Figure 16 Stepper motor connection Figure 17 Controller schematic...

Page 12: ...s located inside the drive in the upper right corner and must be operated with the drive open The test button has different functions depending on how long the button is pressed in 1 Short press 1sec...

Page 13: ...3 3 3 LED Indicator The driver is fitted with a LED indicator see Figure 19 The LED diode can be seen with both open and closed cover Figure 19 LED indicator The statuses of the indicator are shown in...

Page 14: ...Read out the current fault alarm via Modbus Table 13 Purging function activated Test function is activated and stepper motor is receiving control signal for max RPM rotations Hold function is activate...

Page 15: ...analogue 0 10 V input signal The device is factory set for 0 10 V control after detection of a start signal or speed setpoint via Modbus it will automatically shift temporarily to control via Modbus R...

Page 16: ...nication between the controller and AHU are unchangeable only the alternative parameters are to be changed Note the settings of the device delivered with the VTS AHU are prepared by the manufacturer f...

Page 17: ...tuses Adress Function Range Active state 0 Rotorguard Alarm 0 1 1 Alarm 1 V LO Alarm 0 1 1 Alarm 2 V HI Alarm 0 1 1 Alarm 3 I HI Alarm Motor out short 0 1 1 Alarm 4 Temperature High 0 1 1 Warning 8 Ro...

Page 18: ...le 0 100 1 V 13 Config file variant AA ZZ 2 ASCII characters 14 Config file version 100 32000 0 01 15 MOC SW version 0 0 01 16 Rotor Speed Out 0 40000 0 01 RPM 17 Torque 0 1500 0 01 Nm 17 SW variant 1...

Page 19: ...DHX Type 0 1 13 Alternative Modbus ID 1 247 1 14 Alternative BaudRate 0 9600 bps 1 19200 bps 2 38400 bps 3 57600 bps 4 115200 bps 15 Alternative Parity 0 None 1 Odd 2 Even 16 Alternative Stop Bits 0 I...

Page 20: ...oller SPR to work with VTS AHU In order to adapt the brand new RRG controller ordered as a spare part to work with the automation of VTS AHUs you should connect to the RRG controller using a USB RS485...