via Ethernet.
VPA.5030.211
Analog to Ethernet
converter
This unit provides input for 8 analog sensors and
includes power supply. All data will be transferred
via Ethernet.
VPA.5030.311
Modbus to Et
analog to Ethernet
converter
This unit provides input for 8 Modbus device and 8
analog sensors and includes power supply. All
data will be transferred via Ethernet.
4.4
Sensor configuration
Some sensors require configuration before they can be connected to VPVision. Read the sensor's
manual for more information.
Modbus devices
A Modbus device needs to have a unique hardware address in it's daisy chain. Every Modbus sensor
in the same daisy chain requires this unique Modbus address. But every Modbus sensor in the same
daisy chain also requires equal communication settings like baud rate, parity and stop bits for this
daisy chain.
Analog devices
Analog sensor values will need to be converted in to real measurement values. This is done by zero
and span where zero matches 4mA and span matches 20mA. These numbers can be calculated
during the preparation and will be entered in to VPVision during configuration.