© 2021 VPInstruments | MAN-VP-VP38-EN | Revision: 2100 | Date: 25-01-2021
15
Configuration registers
03E8 - 03E8
1000 - 1000 Totalizer reset all
16-bit
Write, any value
03E9 - 03E9
1001 - 1001 Alarm counter reset
16-bit
Write, any value
0422 - 0422
1058 - 1058 Analog output unit
16-bit integer
Read / write
0423 - 0423
1059 - 1059 Analog output mode
16-bit integer
Read / write
044C - 044D
1100 - 1101 Diameter mm
Floating point
Read / write
04B0 - 04B0
1200 - 1200 Modbus address
16-bit integer
Read / write
04B1 - 04B1
1201 - 1201 Modbus multiplier
16-bit integer
Read / write
* Unix epoch time stamp
** Value will only change if both registers are written
Available write operations
Option
Data
Description
4..20 mA
2
3
4
5
6
7
m
3
n/hr
m
3
n/min
mn/sec
ln/min
ln/sec
SCFM