--6-- 

LiFePO4 Batteries:

 

Installation:

 The 

thermal contact

 of sensor and 

inside temperature

 of the battery 

should be well

. Thus, it should be 

screwed down to the 

negative pole

 of the battery, because in most of the cases, this is the cooler side (the positive pole is 

often biased by the exhaust heat of internal fuses of the battery, electronic systems for cell equalization, balancers etc.) 

Function:

 In case of abnormal battery temperatures, such as < -20 °C, > 50 °C, the charging voltage will be reduced strongly 

to the 

safety charging voltage

 of approx. 12.80 V for battery protection, and the maximum charging current rate will be 

halved (safety mode, LED 

"Charge" is flashing

). Any charging data being recorded hitherto will be kept in memory. Battery 

charging is then interrupted, but the supply of consumers being possibly connected will be continued by the charger until 
the battery temperature is again within the acceptable range. After that, automatic charging will be resumed. 
In case of temperatures 

below 0 °C

the charging current will be reduced considerably for battery protection

, the LED 

"Charge"

 will turn off every 2 seconds, and longer charging times can be expected. Also refer to "

Charging Program 4 

for 

"

LiFePO4

 Batteries, Charging Voltage Rates and Temperature Control", 

page 9

 

Warning:  If the charging program LiFePO4 had been set, the temperature sensor must be connected for 
reasons of battery safety. Otherwise, the unit will not operate, and the LEDs 

"Batt.

 

 Full

" and "

Charge

" are 

flashing simultaneously! 

 

"Display" 

6-pole plug-type connector for

 

remote control

Connection (plug and play) of a remote display/remote control is possible for convenient remote control, if the charging 
converter had been installed in a difficult to access location.  

Both units are equipped with a power "limit" function allowing to reduce the charging capacity temporarily at the touch of 
a button (see technical data). 

 

LED Remote Control S 

Order No. 2076

 

7 LEDs for convenient control of functions and charging state. 

 

LCD Charge Control S-VCC 

Order No. 1248

 

With illuminated, excellently readable display showing the state of the charging converter, the current charging 
phase, the voltage of board and STARTER battery and the instantaneous charging current. 

 
 
 

Pilot Lamps: 

"Batt. Full" 

(BOARD battery fully charged,

 green

)**:

 

 

If it is on: 

Battery has been charged to 100 %, trickle charge U2, finished. 

 

If it is flashing: 

Main charging process is effected in the charging phase U1, indication of the charging state of 
75 % (lead), approx. 90 % (LiFePO4) (short flashing), gradual increase to 100 % (long flashing). 

 

Off: 

Main charging process is still being executed in the phase I. 

"Charge" 

(Main charging BOARD battery, 

yellow

)**:

 

 

If it is on: 

Charging converter operates, the BOARD battery is controlled and charged. 

 

If it is flashing: 

Battery Protection:  Battery overtemperature > 50 °C, switchover to low safety charging 
voltage and half of the max. charging current. Automatic return, as soon as the temperature 
is 2 °C less. 

 

If it turns off shortly  

 

every 2 s: 

1.  The power control of the charging converter has reduced the output capacity by more 

than 30 % (STARTER battery discharge protection), since the voltage of the STARTER 
battery dropped below the adjusted value for "Reduction of the charging capacity". The 
charging capacity will be increased automatically, as soon as the voltage exceeds the value 
"increase of the charging capacity". 

 

 

2.  Only LiFePO4:  Battery temperature below 0 °C. The charging current can be reduced for 

battery protection for all modes of charging. If the battery is discharged, longer charging 
times. 

 

Off: 

Charging converter in idle mode. 

 
 

** "Batt. Full"

 and 

"Charge"

 are flashing alternately: 

The battery temperature sensor is not connected with charging program LiFePO4! 

 

 

 

Summary of Contents for VCC 1212-20 C

Page 1: ...charging characteristic line The charging converter excels by its compact design low weight high frequency switch mode boost and buck converter technology and powerfully dimensioned power components for safe operation The simultaneously supplied 12 V consumer loads are protected against overvoltage and voltage fluctuations The integrated recharging branch 12 V 0 1 A provides charging trickle charg...

Page 2: ...ff by the switched 12 V signal No 10 During extended standstill periods and charging of the BOARD battery mains solar the recharging branch of the VCC 1212 20 C 12 V 0 1 A can be used for trickle charging of the vehicle s STARTER battery The 12 V heating cartridge of the refrigerator can be connected to the connector No 10 and 11 during driving while the supply of the refrigerator control is taken...

Page 3: ...led also refer to Function Selection page 5 2 During extended standstill periods and charging of the BOARD battery the recharging branch of the VCC 1212 20 C 12 V 0 1 A is used for trickle charging of the vehicle s STARTER battery Reverse battery 12 V mix up at the large power terminals IN 12 V and OUT 12 V must be avoided in any case This will result in serious damage of the unit Observe the cros...

Page 4: ...rip i e Terminal D 1 Connect it automatic unit control via signal vehicle D 2 Not used automatic unit control via operating voltage Further description function selection see page 2 Unit Settings d Imperatively set the charging program for the BOARD battery type design technology acid gel AGM LiFePO4 from page 8 Start up and Function Test e Further description see page 7 Further operation of the u...

Page 5: ...d by a mains supply charger BLOCKED Also see Function of the Power Control at STARTER Battery and Generator page 7 Battery Temperature Sensor Connect the temperature sensor included in the standard delivery scope to the terminals TS TS any polarity The temperature sensor controls the temperature of the BOARD supply battery Ensure that the installation place of the sensor is not influenced by any s...

Page 6: ...re equipped with a power limit function allowing to reduce the charging capacity temporarily at the touch of a button see technical data LED Remote Control S Order No 2076 7 LEDs for convenient control of functions and charging state LCD Charge Control S VCC Order No 1248 With illuminated excellently readable display showing the state of the charging converter the current charging phase the voltag...

Page 7: ...ery 12 V The unit is equipped with a charging branch which ensures support charging and trickle charging of the STARTER battery 12 V in case of extended standstill periods It will be activated automatically as soon as the BOARD battery had been sufficiently charged for instance by a mains supply charger see Technical Data Recharging Branch A small part of the charger current approx 0 1 A is divert...

Page 8: ... 1 Lead Acid AGM 1 Switch Position U1 14 40 V U2 13 50 V 2 6 h Universal charging program for acid lead acid batteries acc to DIN 57 510 VDE 0510 for charging and trickle charging of supply BOARD batteries Ensures short charging times high charging factor and acid mixing for open standard batteries and closed SLA low maintenance maintenance free non solid electrolyte lead acid drive lighting solar...

Page 9: ...s balancing as well as safety circuit is not admissible The battery temperature sensor must be installed at the battery screw to the negative pole and must be connected at the unit It serves as protection for the battery No function without temperature sensor The LEDs Batt Full and Power are flashing simultaneously If possible the battery temperature should be kept above 0 C 4 LiFePO4 14 4 V Switc...

Page 10: ...he battery charging current is decreased slowly while full charging is increasing The charging converter controls the charging time as well as the charging current From these values and from the course of charging being recorded during the phase I the charging converter determines the 100 full charge point of the battery for automatic switching to U2 In contrast to conventional voltage transformer...

Page 11: ...ee from condensation water Never use the unit in locations where the risk of gas or dust explosion exists Open air operation of the unit is not allowed Lay the cables in a way that damages are excluded and observe to fasten them tightly Never lay 12 V cables and 230 V mains supply cables into the same cable conduit empty conduit Check live cables or leads periodically for insulation faults points ...

Page 12: ... OFF 13 0 V Active at LiFePO4 Board Battery Voltage ON 13 5 V OFF 13 4 V Input TS TS for Battery Temperature Sensor BOARD Yes Quiescent Current Standby 3 7 mA Charging Timer 3 fold Ripple Factor Voltage 30 mV rms Limit of Charging Voltage OUT BOARD Consumer Protection 15 00 V Safety Protection against Short circuit Back Discharge Yes Fitting Position of Unit any Temperature Range 20 45 C Speed con...