VIII.5.c. TABLE
INPUT REGISTER
ENGLISH
Function
Description
Exo type Modbus
address
Bacnet
address
Default
value
System status
Modbus :
0= stop
1= startup
2= low speed startup
3= maximum speed startup
4= normal speed startup
5= in operation
8= o CO2 operation
9= Night cooling
11= shutting down
BACNET :
1= stop
2= startup
3= lo speed startup
4= maximum speed startup
5= normal speed startup
6= in operation
9= CO2 operation
10= Night cooling
12= shutting down
X
3
MSV,40003
External temperature
R
1
AV,40001
Operating temperature of the
blower fan
R
4
AV,40004
Operating temperature of the
recovery fan
R
5
AV,40005
Supply temperature
R
7
AV,40007
Extraction temperature
R
9
AV,40009
Fresh air pressure
LOBBY EC
R
13
AV,40013
Recovery air pressure
LOBBY EC
R
14
AV,40014
CO2
DIVA
R
17
AV,40017
Defrost temperature
R
21
AV,40021
Humidity
R
23
AV,40023
Defrost heater temperature
R
25
AV,40025
Analogue output
0-10 V heating (WATER COIL)
R
54
Analogue output
0-10 V Heat exchanger
R
55
Analogue output
0-10 V Heat exchanger
R
56
Analogue output
0-10 V Supply
R
57
Analogue output
0-10V Recovery
R
58
91