V.5.b. Modification of function parameters (password 2222 required)
V.5.b.1. System control mode
[
(1)
section V.5.a]
Access : Configuration/Control function
The control type is pre-set in the CORRIGO to supply with external compensation It is also possible to switch to recovery
control mode.
(WARNING: if you wish to set the system according to an ambient temperature, select “Recover Ctrl” mode; any
other option will cause a system malfunction)
V.5.b.2. Ventilation parameters
[
(2)
section V.5.a]
Access : Configuration/Ventilation
The ventilation speed is pre-set to 85%. This value can be modified. It is also possible to modify the temperature for
activation of Night Cooling (daytime external temperature/day, etc.) and deactivate it.
V.5.b.3. CO2 setpoint for DIVA QUATTRO option
[
(3)
section V.5.a]
Access : Configuration/Ctrl CO2/COV
The CO2 setpoints are pre-set: LS = 800 ppm HS = 1000 ppm. When the CO2 level reaches 1000 ppm, the system will
increase the operating speed proportionally up to its maximum speed.
V.6. Administrator settings
Activation of the
communication, dehumidification and fire protection
functions requires access to the configuration
menu at system level. Authorization for “Admin” level access is required. Proceed as follows:
Enter the password
1111
using the arrow keys and press OK to confirm. Press the left arrow key twice to access the
menu. In case of error, press C twice and repeat the operation.
Access rights
Enter
Enter the password
1111
For required authorization
Current level:
ADMIN