17
5.4
Tightening torque
It is necessary use a torque wrench or a calibrated screwdriver in order to respect the following tightening torque:
M8 Screw: 27 Nm
•
M10 Screw: 53 Nm
•
M12 Screw: 92 Nm
•
5.5
Tie bars
The Manufacturer markets and provides a specific metal tie bar kit for the ceiling fan, supplied if requested by the
purchaser.
This tie bar kit ensures additional axial stability for the ceiling fan, and keeps it at its height if, due to outside causes,
the machine is stressed anomalously, or the ceiling assembly with just one central pole, does not en-sure adequate
solidity over time
The installation MUST be completed using the tie bar kit for safety reasons, if the purchaser or installer finds any of
the following, in the actual production situation and installation position of the ceiling fan inside the industrial building
involved:
The possibility that the ceiling fan may be struck by gusts of wind (e.g. opening of doors or windows), or that the
•
ceiling fan is installed in buildings that can be opened on the sides
The possibility that the ceiling fan may inadvertently be struck by machines or equipment used by the purchaser
•
or others, working inside the building in which the fan is installed
The possibility that the ceiling fan may be struck by flying creatures, flying around inside the building in which it is
•
installed.
The industrial building is located in an area defined to be seismic or, in any case, subject to apprecia-ble sources
•
of vibrations that affect the building.
WARNING:
Since the assessment of the need to do the installation with an additional tie bar kit depends completely
on objective conditions related to the property, the type of production activity and mode of the same, and these
conditions cannot be ascribed to the Manufacturer, the Manufacturer does not accept any responsibility for not using
the tie bar kit for installation, while stating that its use is preferable and safer.
Installing the ceiling fan in the presence of winds or draughts that strike the machine on the side, with wind speeds
greater than or equal to 14 m/sec, is expressly forbidden. For wind speeds of between 10 and 14 m/sec, use of the
tie bar kit for installation is obligatory, and the machine is already set up for the same.
In the case of strong side winds that strike the ceiling fan, in addition to wind bracing in the form of the tie bar kit, it is
important that the machine is never stopped, but continues to rotate at minimum revs, in order to balance the side
forces that strike it.
We do not advise using the ceiling fan in dusty settings, such as places in which flour or light, easily volatile elements
are present.
5.6
Noise emissions
The acoustic pressure level of pondered emission A in workplaces does not exceed 60 dB(A).
5.7
Cleaning
The machine can be cleaned using products suitable for cleaning aluminium and steel. Each cleaning operation
deemed necessary, must be done with the power supply to the machine disconnected. Suitable precautions must be
taken to avoid subsequent untimely switch-ons during the operations, and operators must wait until the fan has
stopped rotating. Aiming pressurised water towards the ceiling fan for cleaning operations is expressly forbidden,
even though the machine is in class IP65.
5.8
Electrical connection
The installation involves the use of a control unit with an output of 1 - 10 V. However, as an alternative
a manual potentiometer can be used, the only difference being that starting and stopping the machine
must be done manually. Each control unit chosen by the client must be CE certified, or must at least
conform to the low voltage and electromagnetic compatibility directives. Failure to ensure this will
render the warranty null and void, due to damage caused to the machine due to the use of unsuitable material.
However, this choice does not affect the installation procedure described below.
The electrical connection is to be formed by recognised, specialist technicians,
•
authorised in terms of the current norm
Make sure that the characteristics of the electricity supply conform to the indications.
•
It is mandatory to connect the equipment to an effective earth line.
•
The installation must include a device for disconnecting the equipment from the mains
Summary of Contents for Nordik HVSL Super Blade 110 V Series
Page 1: ...NORDIK HVLS SUPER BLADE E SUPER BLADE 110 V Instruction booklet COD 5 571 084 939 23 07 2021 ...
Page 25: ...25 INVERTER MOTOR ELECTRONICS QUICK CONNECTORS ...
Page 28: ...28 Destratification Fan assembly ...
Page 56: ...56 Attachment 2 Electric connection ...
Page 67: ...67 Multi wire diagram for system wiring SINGLE PHASE 85 264V 50 60 Hz ...
Page 78: ......
Page 79: ......