VonHaus 2500446 Instructions Manual Download Page 8

A5P | 01

1.Checks to the area

Prior to beginning work on systems containing 

flammable refrigerants, safety checks are necessary to 

ensure that the risk of ignition is minimized for repair 

to the refrigerating system, the following precautions 

shall be complied with prior to conducting work on 

the system.
Work procedure

Work shall be undertaken under a controlled 

procedure so as to minimize the risk of a flammable 

gas or vapour being present while the work is being 

performed.
2.General work area

All maintenance staff and others working in the local 

area shall be instructed on the nature of work being 

carried out. Work in confined spaces shall be avoided. 

The area around the workspace shall be sectioned off. 

Ensure that the conditions within the area have been 

made safe by control of flammable material.

3.Checking for presence of refrigerant

The area shall be checked with an appropriate 

refrigerant detector prior to and during work, to ensure 

the technician is aware of potentially flammable 

atmospheres. Ensure that the leak detection 

equipment being used is suitable for use with 

flammable refrigerant, i.e. non sparking, adequately 

sealed or intrinsically safe.

4.Presence of fire extinguisher

If any hot work is to be conducted on the refrigeration 

equipment or any associated parts, appropriate fire 

extinguishing equipment shall be available to hand. 

Have a dry powder or CO2 fire extinguisher adjacent 

to the charging area.
5.No ignition sources

No person carrying out work in relation to a refrigerant 

system which involves exposing any pipe work that 

contains or has contained flammable refrigerant 

shall use any sources of ignition in such a manner 

that it may lead to the risk of fire or explosion. All 

possible ignition sources, including cigarette smoking, 

should be kept sufficiently far away from the site of 

installation, repairing, removing and disposal, during 

which flammable refrigerant can possibly be released 

to the surrounding space. Prior to work taking place, 

the area around the equipment is to be surveyed to 

make sure that there are no flammable hazards or 

ignition risks.”No Smoking”signs shall be displayed.

6.Ventilated area

Ensure that the area is in the open or that it is 

adequately ventilated before breaking into the system 

or conducting any hot wok. A degree of ventilation 

shall continue during the period that the work is 

carried out. The ventilation should safely disperse any 

released refrigerant and preferably expel it externally 

into the atmosphere.
7.Checks to the refrigeration equipment

Where electrical components are being changed, 

they shall be fit for the purpose and to the correct 

specification. At all times the manufacturer’s 

maintenance and service guidelines shall be followed. 

If in doubt consult the manufacturer’s technical 

department for assistance.

The following checks shall be applied to installations 

using flammable refrigerants:

- the charge size in accordance with the room size within 

which the refrigerant containing parts are installed;

- the ventilation machinery and outlets are operating 

adequately and are not obstructed
8.Checks to electrical devices

Repair and maintenance to electrical components shall 

include initial safety checks and components inspection 

procedures. If a fault exists that could compromise safety, 

then no electrical supply shall be connected to the circuit 

until it is satisfactorily dealt with. If the fault cannot be 

corrected immediately but it is necessary to continue 

operation, an adequate temporary solution shall be used. 

This shall be reported to the owner of the equipment so all 

parties are advised.

Initial safety checks shall include:

-that capacitors are discharged: this shall be done in a 

safe manner to avoid possibility of sparking;

-that there no live electrical components and wiring are 

exposed while charging, recovering or purging the system;

-that there is continuity of earth bonding

9.Repairs to sealed components

During repairs to sealed components, all electrical supplies 

shall be disconnected from the equipment being worked 

upon prior to any removal of sealed covers, etc.

If it is absolutely necessary to have an electrical supply to 

equipment during servicing, then a permanently operating 

form of leak detection shall be located at the most critical 

point to warn of a potentially hazardous situation.

Particular attention shall be paid to the following to ensure 

that by working on electrical components, the casing is 

not altered in such a way that the level of protection is 

affected. This shall include damage to cables, excessive 

number of connections, terminals not made to original 

specification, damage to seals, incorrect fitting of glands, 

etc.

Ensure that apparatus is mounted securely.

Ensure that seals or sealing materials have not degraded 

such that they no longer serve the purpose of preventing 

the ingress of flammable atmospheres, Replacement 

parts shall be in accordance with the manufacturer’s 

specifications.

NOTE: The use of silicon sealant may inhibit the 

effectiveness of some types of leak detection equipment. 

Intrinsically safe components do not have to be isolated 

prior to working on them.

10.Repair to intrinsically safe components

Do not apply any permanent inductive or capacitance 

loads to the circuit without ensuring that this will not 

exceed the permissible voltage and current permitted for 

the equipment in use.

Intrinsically components are the only types that can be 

worked on while live in the presence of a flammable 

atmosphere. The test apparatus shall be at the correct 

rating.

Replace components only with parts specified by 

manufacturer. Other parts may result in the ignition of 

refrigerant in the atmosphere from a leak.
11.Cabling

Check that cabling will not be subject to wear, corrosion, 

excessive pressure, vibration, sharp edges or any other 

adverse environmental effects. The check shall also take 

into account the effects of aging or continual vibration 

from sources such as compressors or fans.

12.Leakage detection for flammable refrigerants .

Under no circumstances shall potential sources of ignition 

be used in the searching for or detection of refrigerant 

leaks. A halide torch (or any other detector using a naked 

flame) shall not be used.

MAINTENANCE 

Summary of Contents for 2500446

Page 1: ...ren Children should be supervised to ensure that they do not play with the appliance If the appliance is not functioning properly has been dropped damaged left outdoors or immersed in liquid do not use contact DOMU Brands Customer Services Do not use the appliance if any parts appear to be faulty missing or damaged Ensure all parts are securely attached before using the appliance CABLES AND PLUGS ...

Page 2: ...essment authority which authorises their competence to handle refrigerants safely in a accordance with an industry recognised assessment specification Servicing shall only be performed as recommended by the equipment manufacturer Maintenance and repair requiring the assistance of other skilled personnel shall be carried out under the supervision of the person competent in the use of flammable refr...

Page 3: ...A5P 01 COMPONENTS 1 Control Panel 2 3 Colour Digital Display 3 Carry Handle 4 Air outlet 5 Air Inlet with Filter 6 Water Tank 7 Continuous Drainage hole 8 Overflow Pipe 9 Power Supply 1 2 3 8 5 6 4 9 7 ...

Page 4: ... this mode The unit will run continuously SLEEPING MODE In this mode you can adjust the humidity only Press the button and after 10 seconds the indicators will turn dark and the fan speed will be set to low To cancel sleep mode press the mode button again NOTE In sleep mode no error codes will be displayed and the fan speed is not adjustable Humidity HUM This can be adjusted in Aromatic and sleep ...

Page 5: ... not force the castor wheels to move over carpet or attempt to move the unit when it is in operation this may cause the tank to tip over and water to spill causing a hazardous environment 30cm 30cm Button Lock is active Tank Full Indicator Humidity Current Humidity Fan is on Low Fan is on High On Off indicator Sleep Mode Continuous Mode is active Automatic Mode Timer is set ...

Page 6: ...ipe Return the Tank into position for the unit to work and locate the pipe in a suitable place OVERFLOW PIPE WATER TANK WATER DISPOSAL When the Water Tank is full the Indicator will display and the unit will stop automatically Unplug from the mains and remove the tank by holding the grips either side and pulling away NOTE Do not set the tank down as the base is uneven Empty the tank and reinsert i...

Page 7: ...t bristle brush then with clean running water do not use any detergents or abrasive chemicals rinse the filter thoroughly and leave to completely dry for 24 hours CAUTION Do not operate the unit without the fil ter in place and ensure it is completely dry before re installing ...

Page 8: ...e ventilation machinery and outlets are operating adequately and are not obstructed 8 Checks to electrical devices Repair and maintenance to electrical components shall include initial safety checks and components inspection procedures If a fault exists that could compromise safety then no electrical supply shall be connected to the circuit until it is satisfactorily dealt with If the fault cannot...

Page 9: ...ed out prior to leaving the site 16 Decommissioning Before carrying out this procedure it is essential that technician is completely familiar with the equipment and all its detail It is recommended good practice that all refrigerants are recovered safely Prior to the task being carried out an oil and refrigerant sample shall be taken in case analysis is required prior to reuse of reclaimed refrige...

Page 10: ...the lubricant The evacuation process shall be carried out prior to returning the compressor to the suppliers Only electric heating to the compressor body shall be employed to accelerate this process When oil is drained from a system it shall be carried out safely 19 Transport of equipment containing flammable refrigerants Determined by local regulations 20 Discarded appliances supplies flammable r...

Page 11: ...Customer Service for assistance No water is being collected The Unit is set to a lower level than the humidity in the room Temperature too low for water extraction Increase the temperature of the room Check the Unit for blockages Ensure the Unit is not too close to walls or furniture The unit stops regularly The Unit is defrosting allow the Unit to automatically defrost Increase the temperature of...

Page 12: ...ich it is used will invalidate the warranty Returned goods will not be ac cepted unless re packaged in its original packaging and accompanied by a relevant and completed returns form This does not affect your statutory rights No rights are given under this warranty to a person acquiring the appliance second hand or for commercial or communal use COPYRIGHT All material in this instruction manual ar...

Reviews: