PV Module Selection: (Only for the model with built-in MPPT solar charger)
When selecting proper PV modules, please be sure to consider below parameters:
3.
Open circuit Voltage (Voc) of PV modules not exceeds max. PV array open circuit voltage of inverter.
4.
Open circuit Voltage (Voc) of PV modules should be higher than min. battery voltage.
INVERTER MODEL
12Vdc 24Vdc
Max. PV Array Open Circuit Voltage
100Vdc
PV Array MPPT Voltage Range
15~80Vdc
30~80Vdc
Please follow below steps to implement PV module connection:
1.
Remove insulation sleeve 10 mm for positive and negative conductors.
2.
Check correct polarity of connection cable from PV modules and PV input
connectors. Then, connect positive pole (+) of connection cable to positive
pole (+) of PV input connector. Connect negative pole (-) of connection
cable to negative pole (-) of PV input connector.
3.
Make sure the wires are securely connected.
Final Assembly
After connecting all wirings, please put bottom cover back by screwing two screws as shown below.
Communication Connection
Please use supplied communication cable to connect to inverter and PC. Insert bundled CD into a computer and
follow on-screen instruction to install the monitoring software. For the detailed software operation, please
check user manual of software inside of CD.