1.

Locate in accordance with the requirements of the wiring rules relating to
damp situations. National and local council regulations concerning the
discharge of air must also be fulfilled

2.

For installation where external venting is required or is your choice,
select a suitable location in the exterior side wall or under the eave to vent
out the exhausted air/steam and cut out a 

Φ

105mm hole. NOTE: Make

sure the ducting will reach from the centre of installation of the appliance
to the external vent.

3.

Put one end of the 100mm ventiduct through the hole and secure the duct
to a suitable outlet grill and if necessary seal the join with duct tape and
seal space around the hole using a suitable sealant where necessary. Fix
the outlet grill to the wall/eave.

4.

Choose a suitable mounting location in the ceiling and at least 400mm
away from any walls.

Note: the appliance should not be located where it may come into  contact
with water for example above a shower or bath.

5.

Use the template card provided as a hole cutting template
(VBHE-2L: 345x190mm or VBHE-4L: 290x290mm).

6.

The Infra-red lamps heat by direct radiation rather than by heating the air
in the room, so the appliance should be located directly over where drying
occurs.

7.

The appliance has been designed for use on ceilings between 2.4m and
2.7m in height and must be installed with the lowest point at least 2.1m
above the floo

8.

CAUTION: Ensure that the intended hole will have suitable room to locate

the unit and that it will not interfere with joists or the ceiling structure.
Joists, beams and rafters shall not be cut or notched to install the
appliance.

9.

There must be adequate clearances. Make sure a minimum distance of
1m is maintained between the appliance and any illuminated flammable
materials and 400mm between the appliance and any wall. There should
be a minimum of 300mm height clearance in the ceiling for objects
above the housing. A minimum of 30mm clearance is required around
the hole for the appliance, the vertical sides of the appliance and any
adjoining parts of the roof structure, such as joists or insulation batts.

INSTALLATION

Remove all packaging from the appliance before commencing installation. Ensure 
the circuit has been isolated from the mains supply BEFORE commencing work.