OWNERS MANUAL
V.T.E. S.r.l.
PAGURO 12500
12
EXTERNAL CONNECTIONS
The locations of the external connections are shown on the following illustration. The various lines should be of the specified
gauges/diameters, not only to avoid loosening or leakage, but also because using the correct sizes will prevent unnecessary
gaps in the sound-shield that could emit noise.
External connections
DIAMETERS:
Water inlet:
1’’ x 27 mm
Exhaust system:
60 mm
Fuel in:
8 mm
Fuel return:
8 mm
Siphon break:
27 mm
Battery positive:
35 mm
2
Battery negative:
35 mm
2
Main out put voltage:
16 mm
2
VENTILATION
Allow for the sufficient intake of cool air for proper engine combustion and the discharge of the heated air while the
generator is running. Since heated air rises, the intake of cool air should be directed into the lower area of the generator
compartment and the heated air should be discharged from the upper area of the compartment. Minimum clearances of the
generator’s sound-shield hood from the generator compartment’s bulkheads are shown in the illustration. These are the
minimum clearances required to provide adequate ventilation.
NOTE: Engine combustion air enters the generator’s enclosure through holes in the base of the enclosure. This area
must be kept clear of obstructions to help insure air entry.