background image

33

10.1 RELATED DOCUMENTS

 

 BS 5440 

PARTS 1 & 2 

FLUES & VENTILATION REQUIREMENTS 

  BS 5449 

PART 1 

FORCED CIRCULATION OF HOT WATER SYSTEMS 

  BS 5482 

PART 1 

DOMESTIC BUTANE & PROPANE GAS BURNERS IN PERMAMENT DWELLINGS 

  BS 5546 

 

INSTALLATION OF GAS HOT WATER SUPPLIES FOR DOMESTIC PURPOSES  

  BS 6798 

 

INSTALLATION OF BOILERS OF RATED NOT EXCEEDING 60kW

SECTION 10 - LPG INSTRUCTIONS

10.6 CHECKING THE CO

2

 AND ADJUSTING THE 

GAS VALVE

THE GAS VALVE MUST BE SET-UP OR ADJUSTED WITH 
THE AID OF A PROPERLY CALIBRATED FLUE GAS ANA-
LYSER.
Isolate the appliance from the electrical supply and remove 

the appliance casing as described in 4.7.1. Set the lue gas 

analyser to read CO

2

 and insert the probe into the lue analysis 

test point (

Y1-Z1 

ig. 40). Restore the electrical supply to the 

boiler and switch the boiler to the OFF mode.
Have access to the printed circuit board, locate and open the 
closing plug on the dash board 

(L2 

ig. 43

)

, locate and press 

the CO

 

button (see ig. 43 pos. SW1). The appliance will now 

operate in CO

2

 mode for approximately 15-minutes.

10.6.1 CO

2

 FUNCTION SETTINGS

Locate the CO

 

button (see 7.3)

Select the main selector switch in position 

10.3 CONVERTING THE APPLIANCE GAS TYPE

To convert the appliance to another gas type it is necessary to 
change the injector and adjust the gas valve (CO

2

). 

 To change the injector see 6.12.1

 To replace the lange on the silencer (only Vision 30C) see 6.15

 To adjust CO2 values see 10.6

10.4 GAS SUPPLY

The gas supply must be connected to the appliance by a com-

petent LPG installer and must be of suficient size to supply 

the appliance at its maximum output. An existing supply must 
be checked to ensure that it is of adequate size to deal with 
the maximum rated input of this and any other appliances that 
it serves.

10.5 GAS SUPPLY INSTALLATION

The entire installation including the meter must be purged and 
checked for gas tightness.

10.2 TECHNICAL DATA

Gas Pressures

Vision 25C

Vision 

30

C

Inlet pressure

37.0 mbar

37.0 mbar

Heating maximum gas rate (kg/hr)

1.55

1.94

DHW maximum gas rate (kg/hr)

1.94

2.25

Minimum gas rate (kg/hr)

0.39 

0.47

Injector size

3.9 mm

4.3

Silencer lange

27 mm (itted)

29 mm 

CO2 @ maximum output (%)

10.5

10.5

CO2 @ minimum output (%)

10.5

10.5

CO @ maximum output (ppm)

190

250

CO @ minimum output (ppm)

20

25

CO

2

 FUNCTIONS

ACTION ON THE BUTTON

DISPLAY

combustion analysis mode

press once = burner running at maximum heating

ACO

 

 

gas valve maximun setting

press twice = burner running at maximum DHW

ACO

 

 

gas valve minimum setting

press three time = burner running at minimum

ACO

 

 

 

Summary of Contents for Vision C

Page 1: ...ctions THESE INSTRUCTIONS TO BE RETAINED BY USER Vok ra is a licensed member of the Benchmark scheme which aims to improve the standards of installation and commissioning of domestic hot water systems...

Page 2: ...3A 4 Flue system 13 3A 5 Air supply 14 3A 6 Water circulation 14 3A 7 Electrical supply 14 3A 8 Mounting on a combustible surface 14 3A 9 Timber framed buildings 14 3A 10 Inhibitors 14 3A 11 Showers 1...

Page 3: ...tically Dear Customer Your Vok ra Vision boiler has been designed to meet and exceed the very latest standards in gas central heating technology and if cared for will give years of reliable use and ef...

Page 4: ...shows the temperature values Pressure gauge shows the current pressure of your heating system the gauge should be set between 1 and 1 5 BAR When the appliance is oper ating the gauge may rise or fall...

Page 5: ...ADVANCE ON fun ction is active Displayed when the ADVANCE OFF fun ction is active Displays current minutes past the hour Displays current hour of the day 24 hour clock in 30 minute segments lar ge se...

Page 6: ...y of week setting procedure NOTE the time of day is shown on the display and is also indicated on the 24 segmented display as a lashing segment 1 4 CHANGING THE HEATING PATTERN The built in clock is p...

Page 7: ...he programmed heating pattern AUTO ON Heating is in an ON period according to the programmed heating pattern MAN OFF Heating is being controlled manually and is switched constantly OFF MAN ON Heating...

Page 8: ...ow a period of at least two minutes before re setting the appliance 2 6 EXPLANATION OF FEATURES Although the Vok ra Vision has been designed for simplicity of use it utilises the latest in boiler tech...

Page 9: ...r A01 Ignition failure lame not sensed internal fault Final Reset check appliance operation A02 Limit thermostat fault Final Reset check appliance operation A03 Fan tacho signal fault Final Reset chec...

Page 10: ...on open vented systems This booklet is an integral part of the appliance It is therefore necessary to ensure that the booklet is handed to the person responsible for the property in which the applianc...

Page 11: ...nd the boiler will perform a three minute anti cycle timer delay When the request for heat has been satisied the appliance pump and fan may continue to operate to dissipate any residual heat within th...

Page 12: ...mum system volume 74 litres Pre charge pressure 1 bar 2 5 Dimensions Vision 25C Vision 30C Height mm 715 Width mm 405 Depth mm 248 Dry weight kg 27 28 2 6 Clearances Vision 25C Vision 30C Sides 12mm T...

Page 13: ...to the roof lashing As determined by the ixed collar of the vertical terminal R To the side of a boundary 300 mm S To the side of an opening or window on a pitched roof 600 mm T Below an opening or w...

Page 14: ...ansion vessel to accom modate the increased volume of water when the system is heated It can accept up to 8 litres of expansion from within the system generally this is suficient however if the system...

Page 15: ...itted on a wall of combustible mate rial there is no requirement for a sheet of ireproof material to protect the wall 3 9 TIMBER FRAMED BUILDINGS If the appliance is to be itted in a timber framed bu...

Page 16: ...An alternative method of illing the system would be from an independent make up vessel or tank mounted in a position at least 1 metre above the highest point in the system and at least 5 metres above...

Page 17: ...plane see2 9 Areductionmustalsobemadetothemaximumlength see table below when additional bends are used Reduction for additional bends Bend Reduction in maximum lue length for each bend 45 bend 1 3 me...

Page 18: ...REAR FLUE ig 15 rear lue outlet only Using the template provided mark and drill a 125mm hole for the passage of the lue pipe The hole should be drilled LEVEL to ensure any condense luid that forms is...

Page 19: ...ired number of lue extensions or bends up to the maximum equivalent lue length between the boiler and vertical lue assembly see ig 14 Ensure that any horizontal sections of the lue system have a minim...

Page 20: ...e kit for termination The horizontal terminal is supplied with a built in converter box and cannot be shortened A 130mm hole is required for the passage of the concentric terminal through the wall The...

Page 21: ...ad can be used for connection to the electrical supply Connect the ly lead to a fused plug or fused isolator in the following way brown wire to LIVE supply blue wire to NEUTRAL supply green yellow to...

Page 22: ...ectrical supply to the appliance is switched on Ensure any external controls are switched to an ON position and are calling for heat Move the selector switch to the ON position the appliance will now...

Page 23: ...LY AND IS PROPERLY SECURED ENSURE ALL PIPE WORK IS RE CHECKED FOR TIGHT NESS RE FIT APPLIANCE CASING COMPLETE BENCHMARK CHECKLIST FOR UK ONLY Complete details of the boiler controls installation and c...

Page 24: ...n the reverse order 6 7 LOWER AUTOMATIC AIR RELEASE VALVE ig 28 Carry out component removal procedure as described in 6 4 Remove the expansion pipe locking pin B from the pump as sembly and remove the...

Page 25: ...dition taking care to Fig 34 6 13 ELECTRODES ig 34 Carry out component removal procedure as described in 6 4 Remove the air chamber front cover Disconnect the electrode leads and ancillary wiring from...

Page 26: ...removal procedure as described in 6 4 Remove the locking pin Q1 that secures the cover R1 to the hydraulic manifold Using a hooked piece of wire carefully withdraw the by pass cartridge S1 and or DHW...

Page 27: ...unscrew the inlet connection Unscrew the nut E2 Lift the DHW low switch housing from its seating If necessary remove the locking pin F2 from the DHW low switch taking care not to lose the loat contain...

Page 28: ...ow 35 C and 55 C respectively the boiler will ire on minimum 25 power until the primary thermistor exceeds 55 C Thereafter the pump will over run for a period of 30 seconds 7 2 3 HEATING MODE With the...

Page 29: ...emed as immediately dangerous 7 5 CHECKING THE EXPANSION VESSEL Carry out the component removal procedure as described in 6 4 You must ensure that the boiler is completely drained of water Using a sui...

Page 30: ...mpletion of any task that required the disconnection and re connection of any electrical wiring or component these checks must be repeated 7 8 FAULT FINDING Before attempting any faultinding the elect...

Page 31: ...ressed in hundreds e g 25 2 500 rpm GAS VALVE CALIBRATION Connect the boiler to the power supply Open the gas tap Set the function selector to OFF RESET monitor off Remove the screws E remove the casi...

Page 32: ...st the temperature of the heating system indirectly by changing the required room temperature from between 15 C 25 C this will allow the PCB to recalculate the system temperature required the default...

Page 33: ...controls manufacturer and or Vok ra technical department should you require more speciic information on the suitability of a particular control Further guidance on the recom mended practice for the in...

Page 34: ...ssure switch S E Spark electrode TSC2 Ignition transformer 3W 3 way motor F O H T Flow over heat thermostat FS Flue sensor FT Flow thermistor NTC RS Return thermistor NTC brown CN3 blue F Hv 1 2 7 1 C...

Page 35: ...HE APPLIANCE GAS TYPE To convert the appliance to another gas type it is necessary to change the injector and adjust the gas valve CO2 To change the injector see 6 12 1 Toreplacethelangeonthesilencer...

Page 36: ...7 3 However if the CO2 reading is incorrect the minimum gas pressure must be adjusted as follows locate the minimum adjustment screw ig 44 using a suit able screwdriver remove the protection plug usi...

Page 37: ......

Page 38: ...36...

Page 39: ...38...

Page 40: ...ies vokera co uk www vokera co uk www vokera ie Sales General Enquires T 0844 391 0999 F 0844 391 0998 Vok ra Ireland West Court Callan Co Kilkenny T 056 7755057 F 056 7755060 Vok ra Limited reserve t...

Reviews: