background image

Supplied By www.heating spares.co  Tel. 0161 620 6677

22

7.1

CHECKING APPLIANCE OPERATION
When carrying out any repairs or servicing to the
appliance, the relevant commissioning and/or
set-up procedure must be undertaken to ensure
the continued safe operation of the appliance.
Particular attention should be made to ensure
gas soundness, water soundness, and the
electrical integrity of the appliance.

7.2

APPLIANCE MODE OF OPERATION

7.2.1

START-UP
When power is first supplied to the appliance it

will go through a self-purge procedure whereby
the pump, fan, and motorised valve will be
momentarily energised. The boiler will then
operate in either one of the following modes:

DHW pre-heat

Central Heating

DHW operation

NOTE
A DHW request has priority over the other modes
of operation.

7.2.2

PRE-HEAT

When there is no demand for heating or hot water, the
boiler will periodically light to pre-heat the domestic hot
water heat exchanger to approximately 55

°

C

(measured via the cold water inlet sensor). This
ensures that the appliance is at operating temperature
when there is a request for domestic hot water. The
parameter for the allowable temperature drop –
between pre-heat operation – can be adjusted. If the
appliance remains inactive for a period of 24 hours, the
pump and motorised valve will be energised for a few
moments to prevent these components from seizing.
Should the flow temperature sensor fall below 7

°

C the

pump will be energised. If the flow sensor temperature
falls to below 3

°

C the burner will be lit and the appliance

will operate at the minimum output until the temperature
of the flow sensor reaches 10

°

C, whereupon the

pump will continue to run in pump over-run mode.

7.2.3

DOMESTIC HOT WATER MODE
When the appliance is at rest, the motorised valve is
energised to the hot water position, when a demand
for hot water is made the cold water temperature
sensor activates the pump and fan. When the fan is
sensed to be operating correctly, the ignition sequence
commences. The speed of the fan and therefore the
output of the boiler is determined by the temperature
of the water sensed by the return temperature sensor,
consequently a high temperature at the return sensor
results in a lower fan speed.

7.2.4

DHW TEMPERATURE ADJUSTEMENT
The temperature of the hot water outlet can be
adjusted via the operating parameters (see 5.9).
The boiler is also fitted with a flow-rate restrictor
(see fig. 28) that limits the actual flow of hot water

SECTION 7        CHECKS, ADJUSTMENTS, AND FAULT FINDING

to the taps or outlets. This is to ensure that the
boiler maintains a reasonable outlet temperature
even if the tap or outlet is fully open.

However if the incoming mains pressure is
unusually high, it may possible for the flow-rate to
exceed the desired limit, if this situation occurs
the following procedure should be followed:

set the hot water outlet temperature to maximum
(see 5.9);

open the hot water outlet (preferably the bath
tap) fully;

use the adjustable stopcock (fitted on the cold
water inlet) to reduce the flow of water through
the boiler until a reasonable temperature is
achieved.

7.2.5

CENTRAL HEATING MODE
When there is a request for heat via the time clock
and/or external controls the motorised valve and
pump will go through a self-test function this is to
ensure correct operation and valve configuration.
Once the self-test function is complete, the pump
and fan will be activated via the flow temperature
sensor. When the fan is sensed to be operating
correctly, the ignition sequence commences. The
speed of the fan and therefore the output of the
boiler is determined by the temperature of the
water sensed by the flow & return temperature
sensors, consequently a high temperature at the
flow sensor results in a lower fan speed. As the
water temperature increases, the temperature
sensors – located on the flow and return pipes of
the boiler – reduce the fan speed via the electronic
circuitry. Depending on the load, either the water
temperature will continue to rise until the set point
is achieved or the water temperature will fall
whereby fan speed will increase relative to the
output required. When the boiler has reached the
set point, the burner will switch off. The built-in
anti-cycle device prevents the burner from re-
lighting for an adjustable period of time (factory
default is 3 minutes). When the temperature of
the flow sensor falls below the set-point, the
burner will re-light.

7.3

CHECKING/ADJUSTING FAN SPEEDS
To check the fan speeds, you must first access
the engineer mode.  Before entering the appliance
engineer mode, allow the boiler to purge and
preheat the DHW heat exchanger.
The fan speed should only be changed or
adjusted by the commissioning engineer or
service technician (see 5.10).
To access the appliance engineer mode:

press and hold the MODE and STEP buttons

simultaneously, LED 1 should now show ‘C’
(see fig. 17);

whilst continuing to hold down the MODE and

STEP buttons, using the +/- buttons, adjust
LED 2 until it shows ‘33’;

Summary of Contents for Eclipse ESC

Page 1: ...Supplied By www heating spares co Tel 0161 620 6677 Installation Servicing Instructions THESE INSTRUCTIONS TO BE RETAINED BY USER ESC...

Page 2: ...esign pressure 15 5 13 Regulating the central heating system 16 5 14 Final checks 16 5 15 Instructing the user 16 Servicing Page 6 1 General 17 6 2 Routine annual servicing 17 6 3 Replacement of compo...

Page 3: ...e Vokera Eclipse ESC is a combined central heating and domestic hot water condensing boiler which by design incorporates full sequence electronic ignition circulatingpump expansionvessel safetyvalve p...

Page 4: ...speed via the electronic circuitry Depending on the load either the water temperature will continue to rise until the set point is achieved or the water temperature will fall whereby fan speed will i...

Page 5: ...mum flow rate to operate 2 5 l min 2 3 Gas pressure Maximum Inlet pressure G20 20 0 mbar Maximum gas rate 2 76 m3 h Minimum gas rate 0 80 m3 h Injector size single injector with six 3 8 mm holes 2 4 E...

Page 6: ...terminal on the same wall 1500 L Horizontally from a terminal on the same wall 300 M Horizontally from a vertical terminal to a wall 300 N Horizontally from an opening airbrick openable window etc 300...

Page 7: ...gives detailed guidance on this aspect A compartment used to enclose the appliance must be designed and constructed specifically for this purpose An existing compartment cup board may be utilised pro...

Page 8: ...located in accessible positions to facilitate draining of the appliance and all water pipes connectedtotheappliance Thedraincocksmustbe manufactured in accordance with BS 2879 3 6 4 AIR RELEASE POINTS...

Page 9: ...te outlet pipe must be connectedtothedraininaccordancewithbuilding regulations or other rules in force Fig 6 SECTION 4 INSTALLATION 4 1 DELIVERY The appliance is delivered in a heavy duty card board c...

Page 10: ...h 0225720 0225755 0225740 0225745 0225750 0225730 0225735 0225760 Horizontal flue kit for use with add bends extensions 350 500 Telescopic extension 0 5m extension 1 0m extension 2 0m extension 45 ben...

Page 11: ...g an extension to the required length you must ensure that the excess is cut from the plain end of the extension see fig 7B 7C Remove any burrs and check that any seals are located properly You must e...

Page 12: ...flashing plate Flat roof flashing plate Condensate drain kit 0 25m extension pair 0 5m extension pair 1 0m extension pair 2 0m extension pair 45 bend pair 90 bend pair Twin bracket 5 Single bracket 5...

Page 13: ...onto the male spigots of the concentric to twin converter You must ensure that the entire flue system is properly supported and connected Ensure that any horizontal sections of pipe have a 1 fall tow...

Page 14: ...ernal to the appliance are required a competent personmustundertakethedesignofanyexternal electrical circuits please refer to section 8 for detailed instructions ANYEXTERNALCONTROLORWIRINGMUST BE SERV...

Page 15: ...board Ensure that the EARTH wire is left slightly longer than the others this will prevent strain on the Earth wire should the cable become taut Do not remove the 24V link wire between terminals 2 3...

Page 16: ...Check pipe work etc for water soundness 5 6 PRE OPERATION CHECKS Before attempting to initial lighting of the appli ance the following checks must be carried out ensure all gas service valves from th...

Page 17: ...iance also has a range rating facility which can be used to limit the maximum output to central heating if required Please refer to section 7 for more details 5 12 SETTING THE SYSTEM DESIGN PRESSURE T...

Page 18: ...lla tion and commissioning in the logbook supplied with the boiler This is an important document which must be correctly completed and handed to the user Failure to install and commission the applianc...

Page 19: ...section for detailed instruction if required 6 3 REPLACEMENT OF COMPONENTS Although it is anticipated that this appliance will give years of reliable trouble free service the life spanofcomponentswil...

Page 20: ...e 4 screws that secure the PCB housing cover then remove cover After carefully taking note of all wiring connections disconnect all wiring from the PCB Locate and remove the PCB housing securing screw...

Page 21: ...gently lift the burner from its location Replaceinthereverseorder Pleasenote ensure all seals are in good condition taking care to ensure they are replaced correctly Fig 24 6 14 ELECTRODE see fig 25...

Page 22: ...seated properly NOTE It may be prudent to replace the O ring seals and valve cover gasket whenever the divertor valve assembly is disturbed 6 19 CONDENSE TRAP see fig 28 Carry out component removal p...

Page 23: ...to the rear frame The expansion vessel can now be removed Replace in the reverse order Ensure all seals are in good condition taking care to ensure they are replaced correctly 6 23 INPUT PCB STATUS PC...

Page 24: ...imits the actual flow of hot water SECTION 7 CHECKS ADJUSTMENTS AND FAULT FINDING to the taps or outlets This is to ensure that the boiler maintains a reasonable outlet temperature even if the tap or...

Page 25: ...it is to the right LED 2 shows the last two digits of the maximum fan speed press the MODE button until a fixed decimal is shown in LED 1 press and hold the MODE and buttons until L appears in LED 1 p...

Page 26: ...e correct value is displayed ontheCO2 analyser allowtimefortheanalyser to stabilise Using the procedure detailed in 7 3 5 change the fan speed momentarily from maximum to minimum then back to maximum...

Page 27: ...05 06 07 08 09 10 11 12 13 14 15 16 17 24 26 30 31 32 33 36 37 38 41 42 44 60 28 29 61 65 12 18 19 25 Reason for lockout False flame 24V short circuit No flame detected Internal fault PCB Lockout the...

Page 28: ...emetershouldreadapproximately230Vac Ifso proceed to next stage If not see 7 11 4 connect test leads between the Neutral Earth connections at the appliance input board see fig 15 Themetershouldreadappr...

Page 29: ...ity check to identify the location of the fault IMPORTANT These series of checks must be carried out before attempting any fault finding procedures on the appliance On completion of any task that requ...

Page 30: ...230V AT IS THERE PLUG M5 ON INPUT BOARD 230V AT 7 12 4 FAULT FINDING TEST 1A TEST 1A IS THERE AT TERMINALS 1 7 OF 10 14 Vdc PLUG X7 GO TO TEST 1 CHECK CONTINUITY OF RIBBON CABLE REPLACE DISPLAY PCB YE...

Page 31: ...S NO NO NO FAN FAULT DISPLAYED PRESS RESET ENSURE HEAT REQUEST DOES FAN RUN YES NO IS THERE AT RED GREY 30 35 Vdc WIRE OF FAN YES NO REPLACE FAN REPLACE PCB IS THERE AT GREY PINK 4 9 Vdc WIRE OF FAN Y...

Page 32: ...VAC 11 12 OF PLUG X2 CONTINUITY CHECK NO REPLACE PCB DOES BURNER LIGHT YES NO REPLACE RESTART TEST DOES BURNER STAY LIT YES NO NO YES IS IONISATION VOLTAGE ABOVE 2 0 Vdc REPLACE PCB SILICONE PIPE NOZ...

Page 33: ...clock bezel supplied with boiler into the aperture and secure in place with the 2 locking tabs Connect the wires to the clock as shown in fig 35 Mount the clock to the clock bezel using the screws pr...

Page 34: ...NOT BE INTERCHANGED Key R T Room thermostat F Fan P Pump S1 Flow thermistor NTC S2 Return thermistor NTC S3 D H W thermistor NTC L1 Led OK green Fig 36 L2 Led alarm blink red F1 Fusibile 2 AF F se I E...

Page 35: ...Supplied By www heating spares co Tel 0161 620 6677 33 NOTE L N E CONNECTION MUST NOT BE INTERCHANGED CONTROL SWITCHING OF TIME CLOCK AND ROOM THERMOSTAT IS 24 vdc FUNCTIONAL DIAGRAM Fig 37...

Page 36: ...input PCB terminals 2 3 Input PCB Plug X20 on display PCB PLUG or CONNECTION X7A X9 X20 DESIGNATION Connection from main PCB Unused Status LED connection PCB Input PCB Input PCB Input PCB Input PCB I...

Page 37: ...8921 10 2A INLINE FUSE 5 pcs 8968 11 DISPLAY BOARD 8918 12 INSTRUMENTAL PANEL 8346 13 QUICK PRIMER PRESSURE GAUGE 8968 14 HOLE COVER 9709 15 ADHESIVE FILM FOR INSTRUMENTAL PANEL 8349 16 PLASTIC TRADE...

Page 38: ...FUSE 3478 6 CASE CLIP 10 pcs 5588 8 WIRED TRANSFORMER 1048 9 PRESSURE GAUGE 1037 11 PRINTED CIRCUIT BOARD MTN SETTING 10022685 11 PRINTED CIRCUIT BOARD LPG SETTING 10022688 12 3 15A INLET FUSE 8969 1...

Page 39: ...14 HEATING BY PASS VALVE 1734 15 RUBBER DIAPHRAGM 6872 16 FLOW MANIFOLD FRONT PLATE 6853 17 BRASS CAP 8866 18 3 PORT VALVE SPRING 6862 19 O RING 5 pcs 6895 20 SHUTTER FOR 3 WAY 2910 21 WASHER 5 pcs 29...

Page 40: ...3 NTC SENSOR 1194 4 WASHER 10 pcs 5023 5 CONNECTIONS 8873 6 PIPE 1013 7 CONNECTION 9730 8 WASHER 10 pcs 9732 9 PIPE 9731 10 CONNECTION 10022570 11 PIPE 1192 12 SIPHON 1191 13 SILICONE TUBE 1457 14 PRE...

Page 41: ...EXCHANGER 8884 13 WASHER 9287 14 EXCHANGER LOWER INSULATING PANEL 1193 15 COVER FOR HEAT EXCHANGER 1033 16 EXCHANGER UPPER INSULATING PANEL 1016 17 ROOMSEALED CHAMBER 10022672 18 WASHER 8903 19 GLASS...

Page 42: ...AN 1018 11 SCREW 1006 12 SCREW 9292 13 PRESSURE CONNECTION 8915 14 WASHER 9299 15 MAIN BURNER JET MTN 8970 15 MAIN BURNER JET LPG 9295 16 MAIN BURNER JET SUPPORT 1195 17 GAS PIPE 10022442 18 GAS VALVE...

Page 43: ...with the relevant conversion kit the appliance engineer mode If the CO2 reading is incorrect the maximum gas pressure must be adjusted as follows Using a suitable screwdriver very slowly turn the max...

Page 44: ...442 281460 Technical Advice Tel 0141 945 6810 Spare Parts Tel 0141 945 6820 After Sales Service Tel 0870 333 0220 Vok ra Ireland West Court Callan Co Kilkenny Tel 056 55057 Fax 056 55060 Vok ra Ltd re...

Reviews: