background image

25 

 

Radio Test 

This  Menu  is  used  to  test  the  connection  between  the  radio  terminal  and  the 
boiler controller, thus checking the level of electromagnetic pollution. The Radio 
Terminal enters continuous transmission and counts correct and failed responses. 
The signal quality depends on the number of errors (misses). 

Change  code  (only  if  it  is  necessary  to  pair  different  boilers  with 
different thermostats in the same area) 

Code  change  allows  the  remote  control  to  be  matched  to  the  boiler,  so  that  a 
remote  control  is  only  matched  to  a  specific  boiler  allowing  different  boilers  to 
coexist in the same area). To change the code: Section code 

 

Enter  the  Boiler  Learning  Menu  and  learn  the  board  and  press  the 

SET 

key

 

 

Press 

SET 

on the radio thermostat and check the action result 

Contrast 

This Menu allows you to set the display contrast 

Descriptive 

Keys 

Display 

Edit value 

 

 

Save 

SET

 

Exit 

ESC 

Key sound 

Menu to enable or disable key sound. 

Language selection 

Menu to change language. The highlighted language is the one currently defined. 

System menu 

Menu to enter the technical menu. 

It is password protected by installer. 

Press  set  to  enter  edit  mode  and 

to  increase  or 

decrease  the  selected 

digit. Press set to save the digit and move to the other. Press esc to cancel the 
digit  or  exit  the  menu.  If  the  password  is  correct,  the  first  screen  of  the  menu 
appears. 

Menu 

Descriptive 

Auger 

Auger Menu 

Fan combustion 

Combustion Fan Menu 

Exhaust fan 2 

Exhaust Fan 2 Menu 

Fan heating 

Fan Heating Menu 

Thermostats 

Thermostats Menu 

Th extinction 

Thermostats Menu Extinguish 

Timers 

Timers menu 

Activations 

Activations menu 

Air Mass Sensor 

Primary Air Regulator Menu 

Counters 

Counters Menu 

Test Outputs 

Output Tests Menu 

Summary of Contents for TEK Biomasse PIKO

Page 1: ...TEK Biomasse 2022 NG01 EN220705 Instruction Manual Pellet Compact Boiler PIKO ...

Page 2: ...User Menu 1 16 User Menu 2 17 9 2Ways2 Remote Command 20 Control panel 21 9 2 1 The keys 21 9 2 2 Menu 22 9 2 3 Modify room temperature 22 9 2 4 User menu 23 Chrono Menu 26 9 3 1 Modality 26 10 Installing and configuring the 4Heat App 28 System architecture 28 Local call and remote connection 28 Keys and LEDs on 4Heat modules 29 Installation 29 New 4HEAT module configuration 30 Connection to 4HEAT...

Page 3: ...it is available at all times In case of moving or selling the equipment the documentation must be attached and forwarded to the new user owner 2 SECURITY WARNINGS The instructions contained in this manual must be followed both by the Technician Installer Maintenance and by the User Some of the warnings if not followed void the warranty contract Installer Technician and Maintenance Manager The inst...

Page 4: ...ser of the following In case of water leaks it is necessary to turn off the water supply and immediately notify technical support System pressure operation must be checked periodically User Before using for the first time the user must read this manual in its entirety and bear in mind the following Immediately disconnect the equipment from the power supply in the event of a breakdown or malfunctio...

Page 5: ... of components resulting from improper use or negligence lack of maintenance installation in violation of current regulations and laws Use of poor quality pellets or any other similar product in disregard of the provisions of Point 5 Malfunctions resulting from poorly executed repair attempts Forced use of equipment after failure alarm Chimney malfunction Damage caused by tampering with the equipm...

Page 6: ...ds This is the only fuel indicated for this equipment Yield and power vary depending on the quality of pellets used For correct operation you must use pellets according to the characteristics below Technical Fuel Information Pellets Diameter 6mm Length 10 to 30 mm Density in the bag min 650 kg m 3 Humidity Max 10 Max from the ashes Max 1 5 Max from the dust Max 2 3 Calorific value of various fuels...

Page 7: ...u must comply with some essential rules Improper installation will compromise the safety and proper functioning of the boiler When installing the equipment all national and local regulations as well as European standards must be observed Boiler leveling The boiler must be leveled using a bubble water level and using the rubber adjustment feet Installation constraints It must be safeguarded that no...

Page 8: ...ted at the back of the boiler which can be channeled to the outside You must not use bends or tubes with a section smaller than 50mm nor a maximum length greater than 800mm You must also safeguard that this admission will never be obstructed from the outside and that it is at least 20 cm from the ground Outside you should put protection against rain and wind Safeguard the requirements and relating...

Page 9: ... high temperature silicone gasket 200ºC with inverted installation male downwards to prevent condensation from flowing out of the chimney For chimneys over 5 meters high their section must change to a diameter of 150 mm after 5 meters The dimensioning of the smoke duct must be done considering 0 P a The piping used outdoors must be in double walled stainless steel in order to avoid condensation an...

Page 10: ...pansion vessel The connection to the hydraulic network must be carried out as shown in the image below The safety valve must be connected to the sewer taking into account that it must be properly siphoned Figure 7 Hydraulic connection diagram Boiler leakage is carried out through the leakage valve installed in the boiler body being necessary to remove the right side panel Figure 8 Location of the ...

Page 11: ...ves will block these devices It is mandatory to install isolation valves in all hydraulic connections as shown in the image below Electrical installation Installation must be carried out by qualified personnel according to EN 10683 Ensure that the electrical installation has ground connection With the switch off connect the cable to the wall socket and plug Figure 9 Turn on the switch to electrica...

Page 12: ...mpletely to clean the ash Simultaneous use with other ventilation systems see point 9 Installation constraints Safeguarding the safety distance from combustible materials see point 10 Boiler installation site Air supply and smoke evacuation see points 7 4 Air intake and 7 5 Smoke evacuation duct If a fire occurs in the equipment or chimney you must Immediately turn off the equipment Do not open an...

Page 13: ...ice from the mains Attention Ensure that the device is not disconnected from the power supply when it is in operation This process requires that the device is not performing any operations and that the display shows OFF ...

Page 14: ...at modify required temperature increase data Pellet loading correction After 3s press or and confirm P3 P3 Modify combustion power confirm data Manual pellet loading P4 Thermostat modify required temperature decrease data Combustion fan speed correction After 3s press or and confirm P3 LED L1 Led On Fan on L2 Led On Power on L3 Led On Ignition resistor on L4 Led On thermostat temperature reached L...

Page 15: ...ff when it was on Wait for this operation to complete OFF DEL This message notifies you that the planned hours of operation parameter T67 are reached Proceed to cleaning To clear the warning see Reset Clear rCLr CLr Periodic cleaning running Information message that the boiler is performing periodic cleaning PCLr Supply pellets rFiL Open hopper thermostat FLAM Automatic periodic cleaning running P...

Page 16: ...ng press any button Charging stops automatically after 300 seconds Enabled only if A48 0 Pellet loading correction A long press of the P2 button activates this function You have to do this twice to enter the modification mode The bottom display shows PELL the top shows the value With the P2 P4 buttons the value is increased or decreased the factory value is 0 After 5 seconds the new value is saved...

Page 17: ...ekly mode from Mon to Sun FiSE Weekend mode from Saturday to Sunday and from Monday to Friday OFF Disabled modes Time scales programming menu This menu allows programming the time of the chrono mode activated in ModE The word ProG appears on the display PROGRAMMING ProG display Gior Daily Mode Every Day Mo Tu Ue Th Fr Sa Su m o SEtt Weekly mode Monday to Sunday MS FiSe Weekend mode from Monday to ...

Page 18: ...key to confirm values 2 1 3 0 1 I M o 7 Use the P2 key to select the switch off time and repeat the operations from point 5 0 0 0 0 1 I m o For each time program it is possible to change the minutes in 15 minute intervals for example 20 00 20 15 20 30 20 45 Only for 23 00 it is possible to increase minutes from 45 to 59 in order to obtain a light around midnight Time schedule through midnight Set ...

Page 19: ...installation according to the season Remote control TELE OFF This menu allows you to enable and disable the 2Ways or NEO 4T remote control OFF Communication off bidi bidi To communicate with 2Ways thermostat Allows you to communicate with the 2Ways radio thermostat For more information consult the 2Ways manual reset rCLr Menu to reset the timeout of System Maintenance Function It is visible only i...

Page 20: ...sion and reception distance may be reduced in the case of electromagnetically noisy environments other devices such as wireless headphones sender toys or other devices may influence system performance Check for the presence of such instruments and be sure to turn them off in order to avoid electromagnetic wave pollution If more remote thermostats are nearby it is necessary to associate the remote ...

Page 21: ...turn on the screen press the button again Standby By pressing the button for 3 seconds when the main screen is displayed it is possible to completely turn off the remote control and thus reduce battery consumption This feature is to be used in case of prolonged non use of the remote control If this function is activated the boiler will no longer use the ambient temperature as a reference To turn o...

Page 22: ...ntil you reach the main menu if that is the intention If the thermostat cannot communicate with the boiler the message Transfer unsuccessful will appear In this situation approach the boiler and repeat the operation 9 2 3 Modify room temperature Use the keys to change the desired ambient temperature value At the end press the SET key Auger C01 1 0_________ C02 1 2 C03 4 1 C04 5 6 C05 6 2 C06 7 4 S...

Page 23: ...edit the temperature value set for the boiler You can choose the value between the defined minimum and maximum values Buffer Thermostat Deposit Allows you to edit the value defined for the inertia tank or domestic hot water tank It will only be visible if the installation has the tank and if the installer has configured it in one of the following options P26 2 3 4 Summer Winter Option to be define...

Page 24: ...f the wireless radio thermostat Status thermostat Descriptive Activated The radio thermostat is used by the boiler Disabled The system uses the boiler control panel and on the main display the thermostat value and image will disappear Radio Standby Menu to completely turn off the remote thermostat and decrease battery consumption Descriptive Display Press the SET key to activate Standby mode To ac...

Page 25: ...heck the action result Contrast This Menu allows you to set the display contrast Descriptive Keys Display Edit value Save SET Exit ESC Key sound Menu to enable or disable key sound Language selection Menu to change language The highlighted language is the one currently defined System menu Menu to enter the technical menu It is password protected by installer Press set to enter edit mode and to inc...

Page 26: ...et after programming it is necessary to select the desired mode in the mode menu to turn the system on off by Chrono Daily Select the day of the week and schedule the start and end times for each day there are 3 time periods This mode runs 3 different time intervals for each day of the week When you need a program to go past midnight Set the extinguish time for one day at 23 59 and the ignition ti...

Page 27: ...or example the daily mode is set the other modes are not changed time schedule keys After choosing your favorite program Select schedule time Enter modify mode selected time flashes SET Edit the timers Save the program SET Enable Activate the program appears or disabled appears Exit ESC NOTE In order for any chosen time within a mode to work you must activate it by pressing Appears Schedule Daily ...

Page 28: ...to interact with the heating system Local call and remote connection Local connection The connection between the 4HEATModule Wikey or Pinkey and the APP is made over the home Wi Fi network only if both are connected to the same Wi Fi network Remote connection We speak of remote connection when at the time of using the App the user is away from home In this case the App uses your Smartphone s data ...

Page 29: ...e Wi Fi Led a turns Steady Green the device does not communicate correctly with the board make sure that the device is connected correctly and that the heating system boiler stove or stove is connected to the electrical network 3 Wi Fi communication if the Blue LED has a steady light the communication with the application was successful and the device is communicating correctly while in WiKEY we w...

Page 30: ...rary Wi Fi network to which you have to connect with your Smartphone To connect your Smartphone to Wi Fi you have to go to Settings Wi Fi on your Smartphone where the Wi Fi list appears and you have to select WI FI 4HEAT If the Smartphone asks to stay on this Wi Fi network you must accept it otherwise the configuration cannot be done In this way the 4HEAT Module will be linked to the app and the a...

Page 31: ...s are not flashing and then press the button b for 10 seconds Images and descriptions may vary depending on the device you are configuring on After completing the 4HEATModule device installation procedure we recommend that you close the application and restart the app On Apple devices Double press the Start button from the 4HEAT application to close it On Android devices Press the lower right butt...

Page 32: ...s of the 4HEATModule device already configured Operating state OFF Operating state lock Operational status ON Device not connected or inaccessible Update required App management When entering the already configured App a help menu will appear that you can consult as many times as you need for better use Watch our video on installing the 4Heat app https youtu be 9maAK0kYzVY Watch our video on using...

Page 33: ... light or lack of performance it is necessary to clean it daily Carefully clean the brazier ensuring that all holes are clear It is natural for stone to form at the base of the brazier this phenomenon largely depends on the quality of the pellets used Figure 11 Brazier Put the brazier back in place ensuring the perfect alignment of the resistance hole with the respective resistance Incorrect align...

Page 34: ...e ash compartment open the door and open the ash drawer by turning the handle from top to bottom Once the handle is placed horizontally pull out the drawer Carry out the same operation for the lower lid Dump the ash from the drawer and with the aid of an ash vacuum cleaner vacuum the ash compartments ...

Page 35: ...r the bottom box 11 3 1 Semi annual cleaning You must periodically clean the boiler and the smoke collector or for every 600 kg of pellets consumed This cleaning must also include cleaning the smoke extraction fan Remove the turbulators and clean the tubes with a steel brush To access the fume fan loosen the six screws that secure the cover to the left side cover Loosen the eight screws that secur...

Page 36: ...rtance to minimize the effects of corrosion Do not use liquids for cleaning If necessary use a spatula or wire brush beforehand 11 4 1 Chimney cleaning Chimney cleaning should be carried out at least twice a year at the beginning and middle of the winter season or when necessary This cleaning must be carried out with a 100 mm nylon or steel brush Figure 12 Cleaning brush for pellet equipment It is...

Page 37: ... process as if it comes into contact with the metallic structure iron cast iron sheets it can cause corrosion of the structure and or scrape the paint End of season maintenance At the end of the heating season you must have your boiler serviced by a specialized technician This maintenance is intended to ensure the operability of your equipment and ensure the perfect functioning of all its componen...

Page 38: ...re sensor Exceeded boiler water temperature 90ºc Circulator pump blocked air in circuit or any valve closed or blocked Check the installation Wait for the boiler or hopper to cool down and for the message stop or off to appear on the display Er05 Smoke temperature sensor Extinguishing combustion due to excessive smoke temperature Lack of cleaning of the smoke circuit Lack of dissipation obstructed...

Page 39: ... hopper clean the burner and check the resistance against the burner Er15 Lack of supply voltage 230V A power failure has occurred Lack of electricity Check outlet electrical panel Er16 RS485 communication error Occurs when communication between controller and panel fails Lack of communication between panel and controller Check plug or cable Reset and reconnect Er17 Air flow meter error Occurs if ...

Page 40: ...hed excessive chimney draft The use of swivels or fans in the chimney is not allowed Er44 Open door error Check door lock or ash drawer Check the cord Er56 Hydraulic scheme different from boiler configuration SerU Notifies that the planned hours of operation parameter T66 are reached Periodic review is required Call a technician for maintenance and service message reset ...

Page 41: ...41 13 ELECTRIC SCHEME ...

Page 42: ... types of hydraulic configurations These configurations are optional and must be requested at the time of ordering by means of a quote These settings imply that the start up is carried out exclusively by a technician of the Tek Biomasse brand Figure 14 Possible installation diagrams upon quotation ...

Page 43: ...temperature is reached and turning it on again when it drops by 1ºC Figure 15 Installation scheme without DHW To change the installation configuration access the technical menu TPAR PASSWORD TP08 and change the parameters P77 0 Deactivate DHW sensor P26 5 Define installation type without DHW P75 4 0 Enable disable wired remote thermostat In this case the remote thermostat overrides the controller ...

Page 44: ...am below It does not require any additional configuration Figure 16 Installation diagram with DHW NOTE It is not mandatory but in both cases it is recommended to install an anti condensation valve To change the installation configuration access the technical menu TPAR PASSWORD TP08 and change the parameters P77 9 The DHW sensor P26 2 Define installation type with DHW P75 4 0 Enable disable wired r...

Page 45: ...rd product subject to order and on site parameterization by the brand s technician It implies the separate purchase of the Clima 610 unit for operation of the secondary circuit devices Not all models are compatible with this solution so you should contact the manufacturer to verify the boiler s compatibility with this type of solution ...

Page 46: ...46 15 DIMENSIONS OF CONNECTIONS ...

Page 47: ...W 18 3 17 1 6 01 4 95 2 1 1 06 Pellet consumption kg h 4 0 1 37 Autonomy H 15 43 8 Performance 87 91 CO to 13 O 2 ppm 0 01 0 01 Mass flow of smoke g s 14 6 8 47 Minimum chimney draft Pa 12 10 Smoke temperature ºC 164 81 Absorbed electrical power W 250 82 Auger V Hz 230 50 Deposit capacity kg 60 Smoke outlet diameter female mm 100 Diameter hydraulic connections in Only on ignition ...

Page 48: ...48 Authorized Agent Office and Factory 1 Factory 2 Estrada dos Guilhermes 27 Moinho de Vento 1 E 2405 012 Maceira LRA 2405 008 Maceira LRA Portugal Portugal Phone 351 244 770 240 comercial grupovm pt ...

Reviews: