MAINTENANCE AND DIAGNOSIS OF FAILURES
1
MAINTENANCE
Before carrying out any maintenance
operation, disconnect the device from the
power supply.
Frequently check the facility in order to
discover any imbalance or sign of deterioration
or wear. Do not use the device if any repair or
adjustment is necessary.
A record of all repairs and maintenance operations
must be kept. The owner of the facility must keep
these records safe.
Every six months
1
Check that the operation and safety devices, as well
as their installation, have not suffered any damage
from the weather or external agents.
2
Check the operation of the flashing light.
3
Check manual operation.
2
OPERATIONS COUNTER
1
Press ENTER to access the main programming menu.
The display lights up and D1 flashes.
2
Press the buttons ^ and
V
until D1 shows the letter
ç
.
D3 and D4 show the number of operations
completed (see the table).
3
Press ESC to return.
3
FAILURE DIAGNOSIS
D1
D2
Parameter
D3
D4
Pre-
determined
option
Options or values
ç
1
Operations carried out
X
X
Indicates the cycles completed, multiplying
the indicated figure by an amount, for
example:
68
indicates 6,800 cycles completed
6.8
indicates 68,000 cycles completed
Problem
Cause
Solution
The door does not make
any movement when a
key command is given
Absence of system power supply voltage
Reestablish the power supply
F1 blown
D102 (230V, 50Hz): 2.5A;
D102M (125V, 60Hz): 4A
Replace using another fuse of the
same value and investigate the cause
of the failure
Release switch open (the display shows
STOP
)
Check the switch, its adjustment and
cabling
Command devices defective
Check the respective manuals
The door does not open
Door overloaded
Remove the excess load
Door imbalanced
Balance the door
The door does not close
(the display shows
C5
or
Ftço
)
The safety device (photocell or strip) or its
cabling are open or defective
Check th e cabling and device
(photocell or safety strip)
The door cannot
completely close (or
open)
The safety device detects an obstacle
Remove the obstacle and try again
Run not programmed correctly
Programme again