Electrical Control Function
Electrical Control System
123
---T3<52
℃
, the compressor will not limit the frequency and resume to the former frequency.
---T3>60
℃
for 5 seconds, the compressor will stop until T3<52
℃
.
For other models: When T3>65
℃
for 3 seconds, the compressor will shut off. When T3
<
52,the compressor
will restart.
1.3.3 Heating Mode
1.3.2.1 Electronic Expansion Valve (EXV) Control
1.EXV will be fully closed when turning on the power. Then EXV will be standby with 300P open and will
open to target angle after compressor starts.
2.EXV will close with -160P when compressor stops. Then EXV will be standby with 300P open and will open
to target angle after compressor starts.
The unit is working in heating mode with the EXV open 300P(For 12K,it is 480P) for 3 minutes, then
adjusting EXV open angle according to the temperature of compressor discharge every 2 minutes.
1.3.3.2 Outdoor fan running rules:
T4
E
DC_FAN_SSLOW_SPD_ADD
D
DC_FAN_SLOW_SPD_ADD
C
DC_FAN_MIN_SPD_ADD
B
DC_FAN_MID_SPD_ADD
A
DC_FAN_HI_SPD_ADD
21℃
19℃
18℃
16℃
15℃
13℃
12℃
10℃
1.3.3.3 Indoor fan running rules:
For Console(12K):
In heating mode, indoor fan can be selected as high, medium, low, auto and silent. The anti-cold- wind
function has the priority.
When the compressor is running, the indoor fan is controlled as below:
Summary of Contents for ACP-12CC35AECI
Page 2: ......
Page 4: ......
Page 15: ...Service Space 12 Indoor Units 3 Service Space 1000mm 1000mm 1000mm 1000m m ...
Page 18: ...Air Velocity Distributions Reference Data Indoor Units 15 30 42K Cooling Heating ...
Page 19: ...Air Velocity Distributions Reference Data 16 Indoor Units 48 55K Cooling Heating ...
Page 24: ...Field Wiring Indoor Units 21 10 Field Wiring ...
Page 31: ...Wiring Diagrams 28 Indoor Units 4 Wiring Diagrams MTBU 12HWFN1 QRD0W MTB 18HWFN1 QRD0 ...
Page 33: ...Static Pressure 30 Indoor Units 5 Static Pressure MTBU 12HWFN1 QRD0W MTB 18HWFN1 QRD0 ...
Page 34: ...Static Pressure Indoor Units 31 MTB 24HWFN1 QRD0 MTB 30HWFN1 QRD0 ...
Page 44: ...Service Space Indoor Units 41 3 Service Space ...
Page 46: ...Wiring Diagrams Indoor Units 43 Pre setting Instructions ...
Page 55: ...52 Indoor Units 10 Field Wiring ...
Page 59: ...Service Space 56 Indoor Units 3 Service Space ...
Page 60: ...Wiring Diagrams Indoor Units 57 4 Wiring Diagrams ACP 12CC35AECI ACP 18CC50AECI ...
Page 64: ...Field Wiring Indoor Units 61 10 Field Wiring ACP 12CC35AECI ACP 18CC50AECI ...
Page 68: ...Dimensions Console Type 65 2 Dimensions 16 Drain pipe 195 Hanging arm Unit mm 700 600 210 ...
Page 69: ...Service Space 66 Console Type 3 Service Space ...
Page 70: ...Wiring Diagrams Console Type 67 4 Wiring Diagrams MFAU 12HRFN1 QRD0W ...
Page 75: ...Field Wiring 72 Console Type 10 Field Wiring MFAU 12HRFN1 QRD0W ...
Page 81: ...Wiring Diagrams 78 Outdoor Units 4 Wiring Diagrams MOZU 12HFN1 QRD0W MOZU 18HFN1 QRD0 ...
Page 82: ...Wiring Diagrams Outdoor Units 79 MOFU 24HFN1 QRD0 MOYU 30HFN1 QRD0 ...
Page 83: ...Wiring Diagrams 80 Outdoor Units MOYU 36HFN1 QRD0 ...
Page 84: ...Wiring Diagrams Outdoor Units 81 MOYU 36HFN1 RRD0 MOYU 42HFN1 RRD0 ...
Page 85: ...Wiring Diagrams 82 Outdoor Units MOEU 48HFN1 QRD0 MOEU 48HFN1 R MOEU 55HFN1 RRD0RD0 ...
Page 111: ...Refrigerant pipe installation 108 Installation ...
Page 151: ...Troubleshooting 148 Electrical Control System 2 4 4 3 E3 malfunction ...
Page 155: ...Troubleshooting 152 Electrical Control System 2 4 4 8 P1 malfunction For 36k models ...
Page 161: ...Troubleshooting 158 Electrical Control System 2 4 4 14 P7 malfunction ...
Page 174: ...www VIVAX com ...