Troubleshooting
154
Electrical Control System
2.4.4.10. P3 malfunction
P3 display
Current protection of compressor
The protection occurred in
standby
Yes
Yes
Measure whether the
current is normal
?
Yes
No
Replace the outdoor main PCB
Check whether the power
voltage is normal.
Measure whether outdoor
terminal voltage is normal
?
Restart the unit when the power
supply gets normal
No
Yes
No
Reconnect it well
Yes
Measure whether the voltage
between L and N is normal
?
Yes
Measure whether input voltage
of bridge rectifier is normal
?
No
No
Check the wiring of
power wires well or
correctly
Reconnect it well
Check the wiring of
L and N well or
correctly
Reconnect it well
Check the wiring of
bridge rectifier well
or correctly
No
No
Yes
Replace the PFC module(If has)
No
Measure whether the voltage
between P and N is normal
refer
to
the
Appendix
3
?
Replace the bridge
rectifier
No
Check whether
bridge rectifier is
normal
Check the wiring of
reactor or inductance
Reconnect the
wiring
No
Check whether reactor
or inductance is normal
Yes
Replace reactor or
inductance
No
Check whether the outdoor
ambient temperature is
higher than 50
℃
No
Stop the unit
Yes
Check if the outdoor unit
ventilation is good
Yes
Make the outdoor unit ventilate well
Check whether the heat
exchanger is dirty
No
Clean the heat exchanger
Yes
Check whether the refrigerant
system is ok
Replace outdoor main
board
No
No
Check if the outdoor fan
runs properly
please refer to the solution of fan
speed has been out of control
malfunction . Find out the cause and
have it solved.
No
Yes
No
Yes
Yes
Check whether system pressure
is too high
Recycle the over charged
refrigerant
Yes
Summary of Contents for ACP-12CC35AECI
Page 2: ......
Page 4: ......
Page 15: ...Service Space 12 Indoor Units 3 Service Space 1000mm 1000mm 1000mm 1000m m ...
Page 18: ...Air Velocity Distributions Reference Data Indoor Units 15 30 42K Cooling Heating ...
Page 19: ...Air Velocity Distributions Reference Data 16 Indoor Units 48 55K Cooling Heating ...
Page 24: ...Field Wiring Indoor Units 21 10 Field Wiring ...
Page 31: ...Wiring Diagrams 28 Indoor Units 4 Wiring Diagrams MTBU 12HWFN1 QRD0W MTB 18HWFN1 QRD0 ...
Page 33: ...Static Pressure 30 Indoor Units 5 Static Pressure MTBU 12HWFN1 QRD0W MTB 18HWFN1 QRD0 ...
Page 34: ...Static Pressure Indoor Units 31 MTB 24HWFN1 QRD0 MTB 30HWFN1 QRD0 ...
Page 44: ...Service Space Indoor Units 41 3 Service Space ...
Page 46: ...Wiring Diagrams Indoor Units 43 Pre setting Instructions ...
Page 55: ...52 Indoor Units 10 Field Wiring ...
Page 59: ...Service Space 56 Indoor Units 3 Service Space ...
Page 60: ...Wiring Diagrams Indoor Units 57 4 Wiring Diagrams ACP 12CC35AECI ACP 18CC50AECI ...
Page 64: ...Field Wiring Indoor Units 61 10 Field Wiring ACP 12CC35AECI ACP 18CC50AECI ...
Page 68: ...Dimensions Console Type 65 2 Dimensions 16 Drain pipe 195 Hanging arm Unit mm 700 600 210 ...
Page 69: ...Service Space 66 Console Type 3 Service Space ...
Page 70: ...Wiring Diagrams Console Type 67 4 Wiring Diagrams MFAU 12HRFN1 QRD0W ...
Page 75: ...Field Wiring 72 Console Type 10 Field Wiring MFAU 12HRFN1 QRD0W ...
Page 81: ...Wiring Diagrams 78 Outdoor Units 4 Wiring Diagrams MOZU 12HFN1 QRD0W MOZU 18HFN1 QRD0 ...
Page 82: ...Wiring Diagrams Outdoor Units 79 MOFU 24HFN1 QRD0 MOYU 30HFN1 QRD0 ...
Page 83: ...Wiring Diagrams 80 Outdoor Units MOYU 36HFN1 QRD0 ...
Page 84: ...Wiring Diagrams Outdoor Units 81 MOYU 36HFN1 RRD0 MOYU 42HFN1 RRD0 ...
Page 85: ...Wiring Diagrams 82 Outdoor Units MOEU 48HFN1 QRD0 MOEU 48HFN1 R MOEU 55HFN1 RRD0RD0 ...
Page 111: ...Refrigerant pipe installation 108 Installation ...
Page 151: ...Troubleshooting 148 Electrical Control System 2 4 4 3 E3 malfunction ...
Page 155: ...Troubleshooting 152 Electrical Control System 2 4 4 8 P1 malfunction For 36k models ...
Page 161: ...Troubleshooting 158 Electrical Control System 2 4 4 14 P7 malfunction ...
Page 174: ...www VIVAX com ...