The total time is 7 hours, after 7 hours the unit stops
8.11.3 Heating:
The set temperature decrease 1
℃
per hour. Two hours later, the set temperature will maintain as a constant and
the air circulation is kept at low speed (Anti-cold function takes precedence over all).
The total time is 7 hours, after 7 hours the unit stops
8.11.4 Auto:
After an hour running under economic mode, the set temp will rise 1
℃
,if it is under cooling mode; the set temp
will decrease 1
℃
,if it is under heating mode; the set temp will be changeless, if it is under fan-only mode; the
condition will be the same after the air conditioner running under economic mode after 2 hours, and during the
next time the set temp do not change. The total time is 7 hours, after 7 hours the unit stops.
8.12 Auto restart function
In case of a sudden power failure, this function automatically sets the unit to previous settings before the power
failure when power returns
8.13 Turbo mode
In cooling mode, when pressing the turbo button on the remote controller, the unit will enter turbo mode with
ultra-high speed and reach the set temperature more quickly. After running 20 minutes in turbo mode, the indoor
fan will automatically recover the preset speed.