7. Installation details
7.1
Wrench torque sheet for installation
Outside diameter
Torque
mm
inch
Kg.m
φ
6.35
1/4
1.8
φ
9.52
3/8
4.2
φ
12.7
1/2
5.5
7.2
Connecting the cables
The power cord of connect should be selected according to the following specifications sheet.
Grade
Unit
7K
9K
12K
18K
mm
2
1.0
1.0
1.5
2.5
7.3
Pipe length and the elevation
Capacity
Btu/h
Pipe size
Standard
length
(m)
Max.
Elevation
B (m)
Max.
Pipe
length
A (m)
Additional
refrigerant
(g/m)
GAS
LIQUID
07k~09K
3/8
’’
(
φ
9.52)
1/4
’’
(
φ
6.35)
5
8
20
30
12K
1/2
’’
(
φ
12.7)
1/4
’’
(
φ
6.35)
5
8
2
0
30
18K
1/2
’’
(
φ
12.7)
1/4
’’
(
φ
6.35)
5
10
25
30
Caution:
Capacity is base on standard length and maximum allowance length is base of reliability.
Oil trap should be install per 5-7 meters.
In case that
more than
5m.