46 

Starting the engine 

1. Set the ESC switch to "OFF" (1); 
2. Set the air vent knob to "ON" position (2); 

3. Set the 3 in 1switch to 

"CHOCKE" position (3); 

 

Ignition system on; 

 

Fuel circuit on; 

 

Air intake shut-off valves off; 

You don't need air intake shut-off valves to start 
a hot engine. Push the air intake shut-off valves 

knob to the 

"ON" position. 

4. Pull the recoil starter slowly until it snaps into place, 
then pull it quickly; 

Hold  the  carrying  handle  (1A)  firmly  to  prevent 
the  generator  from  falling  off  when  pulling  the 

recoil starter. 

5. After starting the engine, let it warm up until it does 

not stop when the air vent knob returns to the 

"ON" 

position (4); 

Remark: 

 

When starting the engine, with ESC switch turned 
on and there is no charge in the generator: 

 

If you want to work with the Ecothrottle system, 
turn the  Ecothrottle  switch  to  the  "ON"  position 
after the engine warms up for 3 to 5 minutes. 

 

If room temperature is below 5°C, the engine will 
run at the rated rpm (rotations per minute) for 5 
minutes. 

 

If room temperature is above 5°C, the engine will 
run at the rated rpm (rotations per minute) for 3 
minutes. 

 

The  ESC  switch  will  operate  normally  after  the 
above-mentioned periods while it is on. 

Stopping the engine 

1. Switch off the ESC (1); 

2. Disconnect any electrical device; 

3. Turn switch 3 in 1 to 

"OFF" position (2): 

 

Ignition system is off; 

 

Fuel circuit is off; 

4. Turn the air vent knob to the "OFF" position (3) after 
the engine cools down. 

 

Connecting  the  generator  to  an  electrical  wiring  of  a 

building 

The  generator  can  provide  emergency  power  to  a 
residence  when  there  is  an  interruption  in  the  power 
supply from the public grid. When using the generator, 
the aim is not to provide power for all the equipment in 
the house, but to what is considered essential.

 

The connection of  the generator  to the electrical 
wiring  must  be  made  in  a  correct  way  to  avoid 

damage to the generator and avoid the risk of accident. 

Connections  should  only  be  made  by  a  qualified 
electrician  or  by  persons  with  experience  in  electrical 
wiring. They must ensure that the generator is isolated 
from the public grid. 

In the event of a public grid breakdown, whenever you 
connect the generator to a building's electrical wiring to 
supply power, you must turn off general electric circuit 
breaker on the building's main switchboard. 

Do not connect the generator to the electrical wiring of 
a  building  if  it  does  not  have  a  general  electric  circuit 
breaker installed by a qualified technician. 

 If the circuit breaker is not switched off, when the 
public  grid's  power  is  restored,  there  may  be 

returning current in the generator and can cause: 

 

Electrocution to the user or others in contact with 
the generator, 

 

Fire  or  explosion  of  the  generator  and  fire  in  the 
building's electrical wiring; 

The  generator  cannot  be  connected  to  other  power 
sources. 

You must turn off the generator before connecting the 
general  electric  circuit  breaker  in  order  to  use  public 
grid power again.  

 

 

 

 

 

 

 

 

 

Summary of Contents for PRO-POWER VIGI1250

Page 1: ...PT EN GERADOR INVERTER INVERTER GENERATOR ES FR GENERADOR INVERTER GROUPE LECTROG NE INVERTER VIGI1250...

Page 2: ...Aviso de Sobrecarga Vermelha 13 Luz Piloto AC Verde 13 Prote o DC 13 Controlo Inteligente do Motor ESC 13 Bot o de Ventila o 13 Terminal de liga o terra 13 Arranque do motor 14 Paragem do motor 14 Lig...

Page 3: ...iso de Sobrecarga 29 Luz Piloto AC Verde 29 Protecci n DC 29 Control Inteligente del Motor ESC 29 Bot n de la ventilaci n 29 Terminal de conexi n a tierra 29 Arranque del motor 30 Parada del motor 30...

Page 4: ...ntrol ESC switch 45 Air vent knob 45 Ground terminal 45 Starting the engine 46 Stopping the engine 46 Connecting the generator to an electrical wiring of a building 46 Fuel 47 Battery charging 47 Powe...

Page 5: ...ommutateur ESC 62 Bouton de ventilation r servoir de carburant 62 Borne de terre 62 D marrer le moteur 62 Arr ter le moteur 63 Installation d un groupe lectrog ne l installation lectrique d un b timen...

Page 6: ...6 DESCRI O DA FERRAMENTA E CONTE DO DA EMBALAGEM GERADOR INVERTER 1250 VIGI1250 Legenda A Legenda B...

Page 7: ...ques el tricos Perigo de fogo ou explos o Respeite a dist ncia de seguran a Embalagem de material reciclado Recolha separada de baterias e ou ferramentas el tricas Conte do da Embalagem 1 Gerador Inve...

Page 8: ...tru es N o permitida qualquer outra utiliza o que possa ser perigosa e provoque ferimentos no utilizador ou danos no gerador Por motivos de seguran a proibida qualquer altera o ao gerador al m da mont...

Page 9: ...ticularmente as pe as vis veis como por exemplo o dep sito a tampa do dep sito e as uni es das mangueiras flex veis Em caso de fugas ou danos n o ligue o motor de combust o Solicite a repara o do gera...

Page 10: ...igo de ferimentos no utilizador e danos no equipamento N o tape o gerador enquanto estiver em funcionamento De modo a evitar riscos de inc ndio as sa das de ventila o e do escape dever o permanecer de...

Page 11: ...Se retirar componentes ou dispositivos de seguran a para efetuar trabalhos de manuten o estes dever o ser imediatamente recolocados de forma correta Armazenamento no caso de per odos de paragem mais...

Page 12: ...ue o ESC 3 Ligue a ficha AC 4 Certifique se que a luz piloto AC 3B esta ligada 5 Pode ligar o dispositivo el trico O ESC deve ser desligado para aumentar a velocidade do motor para as rpm corretas Se...

Page 13: ...na tomada Reduza a carga do dispositivo el trico conectado abaixo da sa da nominal especificada do gerador se a prote o DC desligar Se a prote o DC desligar novamente pare de usar o dispositivo imedi...

Page 14: ...posi o OFF 3 depois de o motor arrefecer Liga o do gerador instala o el trica de um edif cio O gerador pode fornecer energia el trica de emerg ncia a uma resid ncia quando existir interrup o de forne...

Page 15: ...sconecte a bateria imediatamente e consulte a marca ou o revendedor autorizado Faixa de Aplica o Ao usar o gerador verifique se a carga total est dentro dos valores normais de sa da nominal de um gera...

Page 16: ...Autonomia 50 Dois VIGI2000 3600 watts 4000 watts 3 5 h 6 h Dois VIGI1250 2000 watts 2500 watts 3 5 h 5 2h VIGI2000 e VIGI1250 2800 watts 3250 watts 3 5 h 5 2 h Tabela 2 Caracter sticas de utiliza o in...

Page 17: ...nque Se a fa sca entre os el trodos for fraca ou n o existir fa a o teste com vela nova Se o problema se mantiver com a vela nova repare ou substitua o sistema de igni o 6 Verifique se a anilha de ved...

Page 18: ...al t m de ser devidamente eliminados ou reciclados Certifique se de que um gerador j desativado encaminhado para ser eliminado de maneira tecnicamente correta Antes de mudar o leo encontre um local pr...

Page 19: ...os e precau es do manual de instru es Interven o Di rio 1 m s ou 20 horas 3 em 3 meses ou 50 horas Todos os 6 meses ou 100 horas Todos os anos ou 300 horas Verificar leo do motor Verificar Mudar leo d...

Page 20: ...bstituir a vela de igni o Ajustar a dist ncia dos el trodos Colocar o interruptor do motor na posi o ON Verificar se a vela de igni o est apertada Se n o estiver apertar Limpar substituir o filtro de...

Page 21: ...data de compra Dever pois guardar a prova de compra durante esse per odo de tempo A garantia engloba qualquer defeito de fabrico de material ou de funcionamento assim como os sobressalentes e trabalho...

Page 22: ...22 DESCRIPCI N DE LA HERRAMIENTA Y CONTENIDO DEL EMBALAJE GENERADOR INVERTER 1250 VIGI1250 Leyenda A Leyenda B...

Page 23: ...r Peligro de incendio o explosi n Peligro de quemaduras Respete la distancia de seguridad Embalaje de material reciclado Recogida separada de bater as y o herramientas el ctricas Contenido del Embalaj...

Page 24: ...se describe en este manual de instrucciones No se permite ning n otro uso que pueda ser peligroso y provocar lesiones en el usuario Por motivos de seguridad se proh be cualquier cambio en la m quina a...

Page 25: ...e especialmente de las partes visibles como el dep sito el tap n del dep sito los conectores de las mangueras y la bomba manual de combustible del carburador En caso de fugas o da os no ponga en march...

Page 26: ...ci n y de escape deber n permanecer libres de obstrucciones No modifique las piezas que puedan aumentar o disminuir la velocidad establecida por el fabricante Utilizaci n en el trabajo Apague el motor...

Page 27: ...n un compartimento cerrado Durante el funcionamiento el escape se calienta extremadamente y permanece as durante unos minutos despu s de apagar el motor Evite tocar el tubo de escape mientras est cali...

Page 28: ...ncendido 5 Puede conectar el dispositivo el ctrico El ESC debe estar desconectado para aumentar la velocidad del motor a las rpm correctas Si el generador est conectado a varias cargas o consumidores...

Page 29: ...en el enchufe OFF Sin tensi n en el enchufe Reduzca la carga del dispositivo el ctrico conectado por debajo de la salida nominal especificada del generador si la protecci n DC se apaga Si la protecci...

Page 30: ...i n del generador a la instalaci n el ctrica de un edificio El generador puede suministrar energ a el ctrica de emergencia a una residencia cuando se interrumpe el suministro de energ a de la red p bl...

Page 31: ...r a inmediatamente y consulte la marca o el distribuidor autorizado Rangos de operaci n Al usar el generador aseg rese de que la carga total est dentro de los valores normales de salida nominal de un...

Page 32: ...Autonom a 50 Dos VIGI2000 3600 watts 4000 watts 3 5 h 6 h Dos VIGI1250 2000 watts 2500 watts 3 5 h 5 2h VIGI2000 e VIGI1250 2800 watts 3250 watts 3 5 h 5 2 h Tabla 4 Caracter sticas individuales de u...

Page 33: ...adecuada 5 Realice una prueba de buj as Conectar la buj a a la tuber a Mantenga el electrodo de la buj a en contacto con el cuerpo de la motocicleta y tire simult neamente de la manija del sistema de...

Page 34: ...paratos el ctricos en la basura dom stica Los residuos como el aceite viejo el combustible el lubricante los filtros y las piezas de desgaste pueden da ar a los seres humanos los animales y el medio a...

Page 35: ...dimientos y precauciones del manual de instrucciones Intervenci n Diario 1 mes o 20 horas 3 en 3 meses o 50 horas Todos los 6 meses o 100 horas Todos los a os o 300 horas Verificar el aceite del motor...

Page 36: ...a Ajuste la distancia de los electrodos Ponga el interruptor del motor en ON Compruebe que la buj a est bien apretada Si no apriete Limpiar reemplazar el filtro de aire Desenroscar la buj a y secarla...

Page 37: ...garant a de esta m quina es de dos a os a partir de la fecha de compra Por lo tanto debe conservar el comprobante de compra durante ese per odo de tiempo La garant a cubre cualquier defecto de fabric...

Page 38: ...38 TOOL DESCRPITION AND PACKAGING CONTENT INVERTER GENERATOR 1250 VIGI1250 Figure A Figure B...

Page 39: ...explosion Respect the safety distance Package made from recycled materials Batteries or power tools should not be disposed of together with household waste Packaging content 1 Inverter Generator VIGI...

Page 40: ...e and knowledge of the inverter generator or others unfamiliar with the usage instructions The generator may only be used as stated in this instruction manual Any other use which may be dangerous and...

Page 41: ...nstruction manual Before switching on the generator check the leak tightness of the fuel system particularly the visible parts such as tank tank cap and hose couplings and the hydraulic system hydraul...

Page 42: ...Do not modify parts that could increase or lower the speed set by the manufacturer Use at work Switch off the combustion engine if Whenever you intend to physically move away from the generator or if...

Page 43: ...extremely hot and remains so for a few minutes after switching off the engine Avoid touching the exhaust while it is hot Never store the equipment with petrol in the tank inside a closed space Petrol...

Page 44: ...tched on 5 You can switch on the electrical device The ESC switch should be switched off to increase engine speed to the correct rotations per minute If the generator is connected to several loads or...

Page 45: ...utton ON With voltage in the socket OFF Without voltage in the socket Reduce the charge of the connected electrical device below the specified output of the generator if the DC protector shuts down If...

Page 46: ...knob to the OFF position 3 after the engine cools down Connecting the generator to an electrical wiring of a building The generator can provide emergency power to a residence when there is an interrup...

Page 47: ...or shuts off again disconnect the battery immediately and consult the brand or authorized dealer Power range When using the generator verify that the total power is within the normal rated output volt...

Page 48: ...watts 4000 watts 3 5 h 6 h 2 VIGI1250 2000 watts 2500 watts 3 5 h 5 2h VIGI2000 and VIGI1250 2800 watts 3250 watts 3 5 h 5 2 h Table 6 Generator s individual operation features Generator Rated power M...

Page 49: ...y and simultaneously pull the handle of the recoil starter If the spark between the electrodes is weak or non existent test with a new spark plug If the problem remains with the new spark plug repair...

Page 50: ...rm humans animals and the environment and as such must be properly disposed of Make sure that the deactivated equipment is forwarded for disposal in a technically correct way Before changing the oil f...

Page 51: ...to the user or death Always follow the procedures and precautions in the instruction manual Intervention Daily 1st month or 20 hours Every 3 month or 50 hours Every 6 months or 100 hours Every year or...

Page 52: ...eck the connection between the cable and the plug Clean replace the spark plug Adjust the distance between electrodes Set the engine switch to ON Check that the spark plug is screwed If not screw it C...

Page 53: ...ty of this machine is two years from the date of purchase You should therefore keep your proof of purchase during this period of time The warranty covers any manufacturing defect in material or operat...

Page 54: ...54 DESCRIPTION DE L QUIPEMENT ET CONTENU DE L EMBALLAGE GROUPE LECTROG NE INVERTER 1250 VIGI1250 Figure A Figure B...

Page 55: ...nterdiction d allumer et fumer Danger de choc lectrique Risque d incendie ou d explosion Respectez la distance de s curit Emballage de mat riel recycl Collecte s par e des batteries et ou des outils l...

Page 56: ...oit tre utilis que de la fa on d crite dans ce mode emploi Toute autre utilisation pouvant tre dangereuse et pouvant causer des blessures l utilisateur ou endommager le groupe lectrog ne est interdite...

Page 57: ...vant de commencer travailler Assurez vous que le groupe lectrog ne soit utilis e uniquement par des personnes ayant connaissance du mode d emploi V rifiez l tanch it du syst me de carburant en particu...

Page 58: ...st en marche La charge connect e au groupe lectrog ne doit tre conforme la capacit du groupe lectrog ne Une surcharge du groupe lectrog ne l endommagera ou r duira sa dur e de vie Le groupe lectrog ne...

Page 59: ...s risquez de vous blesser ou d endommager le groupe lectrog ne En cas de doute vous devez contacter un revendeur officiel Pour des raisons de s curit les composants du carburant tuyaux r servoir bouch...

Page 60: ...t en bonne condition Les quipements et les rallonges d fectueux peuvent provoquer des chocs lectriques Si un quipement commence fonctionner de fa on irr guli re s il ralentit ou s arr te soudainement...

Page 61: ...tricit pour prot ger le groupe lectrog ne et tout appareil lectrique connect Le t moin d alimentation CA 3B s teint et le voyant de surcharge rouge reste allum mais le moteur ne s arr te pas de tourne...

Page 62: ...il de capacit ad quate comme indiqu ci dessous 0 12 mm 1 A Par exemple pour 20 A utiliser un fil de 2 4 mm D marrer le moteur 1 Placez le commutateur ESC sur la position OFF 1 2 Placez le bouton de ve...

Page 63: ...rant install par un technicien qualifi Si le disjoncteur principal n est pas coup lorsque le courant du r seau est r tabli il peut y avoir des courants de retour dans le groupe lectrog ne et provoquer...

Page 64: ...du groupe lectrog ne Si le groupe lectrog ne doit fournir d nergie au mat riel m dical vous devez d abord obtenir des conseils aupr s du fabricant d un professionnel de la sant ou d un directeur g n r...

Page 65: ...elques minutes Ensuite mettez l interrupteur 3 en 1 et le bouton de ventilation sur la position OFF 7 Enlevez les vis et ensuite le bouchon 8 Enlevez le bouchon du r servoir d huile 9 Placez un bac hu...

Page 66: ...et le couvercle d acc s la bougie Rangement et nettoyage La pr paration du rangement sur de longues p riodes est essentielle pour viter les probl mes et augmenter la dur e de service du groupe lectrog...

Page 67: ...ez vous qu un groupe lectrog ne d j d sactiv est rout pour tre limin d une mani re techniquement correcte Avant de changer l huile trouvez un endroit appropri pour mettre l huile usag e Ne pas le jete...

Page 68: ...c dures et les pr cautions indiqu es dans le mode d emploi Intervention Chaque jour 1er mois ou 20 heures Tous les 3 mois ou 50 heures Tous les 6 mois ou 100 heures Chaque ann e ou 300 heures V rifier...

Page 69: ...ion entre le c ble d allumage et la fiche Nettoyez remplacez la bougie d allumage R glez la distance des lectrodes Placez l interrupteur du moteur sur la position ON V rifiez que la bougie d allumage...

Page 70: ...et appareil est de deux ans partir de la date d achat Vous devrez pourtant garder la preuve d achat pendant cette p riode de temps La garantie englobe n importe quel d faut de fabrication du mat riel...

Page 71: ...cordo com as seguintes normas ou documentos normativos EN ISO 8528 13 2006 e9 2016 1628 2017 656SHB3 P 1036 01 EN 55012 2007 A1 e EN 61000 6 1 2007 conforme as diretivas Diretiva 2006 42 EC Diretiva M...

Page 72: ...VIGI1250_REV01_MAI20...

Reviews: