VT-PTZ10
14
2.6 Principle of Termination
Every device that is connected at the end of the communication data line must be
terminated by either the DIP switch setting or an appropriate device such as a
termination jumper to prevent potential control signal errors.
See Figure 6 for termination switch settings and Figure 7 for examples of devices
requiring termination. Note: Total length of the cable for communication should not
exceed 1.2Km or .74 mile.
** Unless communication error, put the position 2, 3 of the S5 in OFF state.
Position 2, 3 should be set as a pair. (Both 2, 3 to ON position or OFF position)
Figure 7 - Setting Dome Camera Termination
S5
D1
D2
D3
D4
Terminated
Not
Used
X
X
ON
Not terminated
X
X
OFF
Pull Up/Down **
ON
ON
X
Normal **
OFF
OFF
X
Summary of Contents for VT-PTZ10
Page 43: ...VT PTZ10 42 Figure 10 Dimension...
Page 48: ......
Page 49: ......
Page 50: ......
Page 52: ...28492 CONSTELLATION ROAD VALENCIA CA 91355 WWW VITEKCCTV COM 888 VITEK 70...